Minilec ALV D2 Phase Failure Relay
- Brand
- Minilec
- Model number
- ALV D2
- Category
- Protection & Monitoring Relays
Minilec ALV D2 phase failure relay with 2 CO output. Typical uses: AC & R chiller compressor motors, AHU fan /pump motors, hoist & crane.
Price and availability on request
Key features
- Phase Failure, Phase Sequence
- Fixed unbalance settings
- Adjustable UV/OV settings
- Auto Reset, 2 CO output relay
Specifications
| Output Contacts | 2 CO |
|---|---|
| Under Voltage | For 380-440V AC For 220-240V AC For 110 V AC 80% to 95% (adjustable) ; For 380-440V AC For 220-240V AC For 110 V AC 105% to 120% (adjustable) |
| Resetting Mode | Auto Reset |
| Weight | 400 gms. |
| Note | Wherever not specified Contact Rating : 5A @ 230 V AC (resistive) |
| System | 110 / 240 / 380 / 415 / 440 V AC ±20%, 50 / 60 Hz |
|---|---|
| Auxiliary | 110 V (Fixed) or (220 - 230 - 240) or (380 - 415 - 440) V AC ±20% selectable |
| Phase Sequence | Yes |
|---|---|
| Phase Unbalance | 40 V ±6 V (fixed) |
| On Phase Failure | 3.5 secs. ± 1.5 sec |
|---|---|
| On UV/OV | Less than 2 secs. |
| Overall (L x W x D) | 76 x 56.5 x 117.5 |
|---|---|
| Mounting (L x W) | 67 x 46 / 35 mm rail Mounting |
| Applications | AC & R Chiller compressor motors, AHU Fan /Pump Motors, Hoist & Crane, Machinery using multiple small motors, MAIN powers supply distribution panel board, DG Set application, Submersible Pumps, UPS |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.