Minilec S2 DVMR Phase Failure Relay
- Brand
- Minilec
- Model number
- S2 DVMR
- Category
- Protection & Monitoring Relays
Minilec S2 DVMR phase failure relay with (1 CO + 1 CO) / 2 CO output. Typical uses: hoist motor control, 3 ph. split AC machines, agricultural pump starters.
Price and availability on request
Key features
- Phase Failure
- Phase Sequence Reversal
- Voltage Unbalance
- Under Voltage
- Over Voltage
- Under Frequency
- Over Frequency
- Neutral Fail
Specifications
| Display | LCD (3 Digit Liquid Crystal Display With Backlight) |
|---|---|
| Resetting Mode | Auto / Manual Reset |
| Enclosure | S2 FR GRADE Enclosure |
| Weight | 150 gms. approx. |
| Note | Display backlight flashes (ON & OFF) if the unit trips due to any fault. ; Wherever not specified Contact Rating : 5A @ 250 V AC (resistive) |
| System | 100 - 120 / 220 - 240 / 380 - 440 VAC -25%, +20% (3 Ph. 3W / 4W) |
|---|---|
| Auxiliary | Built-in |
| Frequency | 45 - 65 Hz |
| Power Consumption | 25 VA max. |
| Output Relay Contact | (1 CO + 1 CO) / 2 CO |
|---|---|
| Contact Rating | 5A @ 250 VAC / 30 VDC (Resistive) |
| Monitoring | PH - PH Voltages OR PH - N Voltages (Software Selectable) |
|---|---|
| Protections | Phase Failure, Phase Sequence Reversal, Voltage Unbalance, Under Voltage, Over Voltage, Under Frequency, Over Frequency, Neutral Fail |
| Display Parameter | Rotational display of PH - PH Voltages OR PH - N Voltages |
|---|---|
| Resolution (Voltage) | 1 V |
| Resolution (Frequency) | 1 Hz |
| Display Accuracy | ± (1% ± 5 Volts) of actual voltage |
| UV / OV / UB | ± 2% of set value |
|---|---|
| Power On Delay / Trip Delay | ± 5% of set value (± 1 sec for 1 to 10 Sec Ranges) |
| ON (Green) | Power ON |
|---|---|
| TRIP (Red) | Relay Trip due to any fault |
| Operating Temperature | -5 °C to + 60 °C |
|---|---|
| Storage Temperature | -10 °C to + 60 °C |
| Humidity | Up to 95% R.H. |
| Mounting | 35 mm Din Rail mounting |
|---|
| Overall (L x W x H) | 93 x 35 x 61 |
|---|
| Terminals | Suitable for 2.5 sq.mm cable |
|---|---|
| Torque | 0.6 Nm max. |
| Applications | Hoist Motor Control, 3 Ph. Split AC machines, Agricultural Pump Starters, Machine Tools, Valve Actuator Motor, Injection Molding M/c |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.