Minilec D2 VMR2 Phase Failure Relay
- Brand
- Minilec
- Model number
- D2 VMR2
- Category
- Protection & Monitoring Relays
Minilec D2 VMR2 phase failure relay with 2 CO output. Typical uses: AC & R chiller compressor motors, AHU fan /pump motors, hoist & crane.
Price and availability on request
Key features
- Phase Failure, Phase Sequence
- Adjustable Unbalance, UV / OV Settings
- Neutral Fail, Auto / Manual Reset
- Suitable for 3 Ph 4W System
- 2 CO Output Relay
- Fail Safe / Non Fail Safe Logic
- Microcontroller Design
- Adjustable Trip Delay
Specifications
| Output Contacts | 2 CO |
|---|---|
| Under Voltage | 380-440V AC 220-240V AC 100-120V AC 165-245V AC 95-135V AC 45-65V AC |
| Over Voltage | 380-440V AC 220-240V AC 100-120V AC 230-310V AC 130-170V AC 60-80V AC |
| Resetting Mode | Auto/ External Manual Reset (External NC Push Buttons) |
| Weight | 300 gms. |
| Note | Wherever not specified Contact Rating : 5A @ 230 V AC (resistive) |
| System | 100-120 / 220-240 / 380-440V AC -25%+20%, 48-63 Hz |
|---|---|
| Auxiliary | Built In (from 3 Phase) |
| Phase Sequence | Yes |
|---|---|
| Phase Unbalance | 4 % - 20 % |
| Phase Failure | Instant |
|---|---|
| UV/OV | 1 to 10 Sec |
| NF | 2 Sec ± 1.5 Sec. |
| Overall (L x W x D) | 76 X 56.5 X 117.5 |
|---|---|
| Mounting (L x W) | 67 x 46 / 35 mm rail Mounting |
| Applications | AC & R Chiller compressor motors, AHU Fan /Pump Motors, Hoist & Crane, Machinery using multiple small motors, MAIN powers supply distribution panel board, DG Set application, Submersible Pumps, UPS |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.