Metrel MI 3295 Step / Contact Voltage Measuring System

Brand
Metrel
Model number
MI 3295

Two-unit system (MI 3295S current source up to 55 A and MI 3295M meter) for step and contact voltages, earth resistance of large grounding systems, specific earth resistance, potential and clamp current.

Price and availability on request

Request a quote

Sent with the product details: Metrel MI 3295 Step / Contact Voltage Measuring System.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Step voltage
  • Contact voltage
  • Specific earth resistance
  • Earth resistance
  • Potential
  • Leakage current
  • Accurate: high accuracy of the measurements due to a high current of up to 55 A and effective suppression of noise
  • Noise immunity: excellent immunity even against changing earth currents
  • Autonomous Step Voltage meter: no need for long potential leads; a few meters can be used simultaneously
  • Safe: high safety due to low output voltage (55 V)
  • Low weight: the weight of the Station is 29.5 kg only
  • Memory: up to 1000 test results can be saved into the 3-level internal memory of the system
  • PC SW Metrel ES Manager or HVLink PRO included in the standard set enables downloading and analysis of results and printing of test reports

Specifications

Step / contact voltage
Measured Um0.01 mV ... 59.9 V; ±⁠(2 % of reading + 2 digits)
Calculated U0.0 ... 999 V
Station MI 3295S
Test current / voltage / frequency55 A max / < 55 V / 55 Hz
Current0.00 ... 99.9 A; ±⁠(3 % of reading + 3 digits)
Earth resistance
Resistance to earth0.001 ... 199.9 Ω; ±⁠(2 % of reading + 5 digits) up to 99.9 Ω
Specific earth resistance0.00 ... 99.9 kΩm (calculated)
Meter MI 3295M
Potential0.01 mV ... 59.9 V
Current with iron clamp A 1018 / flex clamp A 15871.0 mA ... 9.99 A / 10.0 mA ... 50.0 A
General
Station power supply / communication230 V / 50 or 60 Hz / RS232
Memory1000 memory locations
Overvoltage categoryCAT II / 300 V
Supplied with
MI 3295 Standard setInstruments; MI 3295M and; MI 3295 S; Mains cable; Step voltage probe (25 kg), 2 pcs:; Current earth spike (A 1353); A 1529, 2 pcs; Potential earth spike, 60 cm; A 1629, 2 pcs; Current test lead, 50 m, black, 10 mm2, with crocodile clip, on reel, A 1325; Current test lead, 10 m, black, 10 mm2, with crocodile clip, A 1392; G clamp; Test lead, black, 2 x 3 m (A 1530); Test lead, green, 10 m; Test lead, black, 1.5 m; Test lead, red, 50 m; Connection lead with crocodile clip, red, 1 m; Crocodile cli

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.