Mean Well RST-5000-48 Power Supply 48 V, 105 A, 5040 W, 3-Phase Input

Model number
RST-5000-48

Mean Well RST-5000-48, a 3-phase input power supply from the RST-5000 series for 196-305 / 340-530 V AC input, up to 90.5% efficient, for high-power industrial systems on a 3-phase supply.

Price and availability on request

Request a quote

Sent with the product details: Mean Well RST-5000-48 Power Supply 48 V, 105 A, 5040 W, 3-Phase Input.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • 3ψ 3-wire / △ 196~305VAC or 3ψ 4-wire / Y 340~530VAC wide input range
  • Built-in active PFC function
  • High efficiency up to 90.5%
  • Forced air cooling by built-in DC fan
  • Output voltage and constant current level programmable
  • Active current sharing up to 20000W (3+1)
  • Built-in remote ON-OFF control / Remote sense / Auxilary power / Alarm signal
  • Protections: Short circuit / Overload / Over voltage / Over temperature / Fan fail
  • 5 years warranty

Specifications

Output
DC voltage48V
Rated current105A
Current range0 ~ 105A
Rated power5040W
Ripple & noise (max.)200mVp-p
Voltage adj. range47 ~ 57.6V; Can be adjusted via built-in potentiometer
Voltage tolerance±1.0%
Line regulation±0.5%
Load regulation±0.5%
Setup, rise time2200ms, 80ms at full load
Hold up time (typ.)20ms / 230VAC at 75% load 14ms / 230VAC at full load
Input
Voltage range3ψ 3-wire / △ 196 ~ 305VAC or 3ψ 4-wire / Y 340 ~ 530VAC
Frequency range47 ~ 63Hz
Power factor (typ.)0.95/230VAC(400VAC) at full load
Efficiency (typ.)90.5%
AC current (typ.)15A/230VAC(3ψ 3-wire / △) 9A/400VAC(3ψ 4-wire / Y)
Inrush current (typ.)75A/230VAC(3ψ 3-wire / △) 50A/400VAC(3ψ 4-wire / Y)
Leakage current<3.5mA/△305VAC(Y 530VAC)
Protection
Overload100 ~ 112% rated output power; User adjustable continuous constant current limiting or constant current limiting with delay shutdown after 5 seconds, re-power on to recover
Over voltage60 ~ 67.2V; Protection type : Shut down o/p voltage, re-power on to recover
Over temperatureShut down o/p voltage, recovers automatically after temperature goes down
Function
Remote senseCompensate voltage drop on the load wiring up to 0.3V. Please refer to the Function Manual.
Current sharingUp to 20000W or (3+1) units. Please refer to the Function Manual.
Voltage programmableAdjustment of output voltage is allowable to between 20 ~ 120% of nominal output voltage. Please refer to the Function Manual.
Constant current level programmableAdjustment of constant current level is allowable to between 20 ~ 100% of rated current. Please refer to the Function Manual.
Auxiliary power(AUX)12V@0.1A(Only for Remote ON-OFF control)
Remote ON-OFF controlPlease refer to the Function Manual.
Environment
Working temp.-30 ~ +70℃ (Refer to "Derating Curve")
Working humidity20 ~ 90% RH non-condensing
Storage temp., humidity-40 ~ +85℃, 10 ~ 95% RH non-condensing
Temp. coefficient±0.03%/℃ (0 ~ 50℃)
Safety & EMC
Safety standardsUL62368-1, CAN/CSAC22.2 No. 62368-1, TUV BS EN/EN62368-1, EAC TPTC 004 approved
Withstand voltageI/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
Others
MTBF293.3K hrs min. Telcordia SR-332 (Bellcore) ; 34.7K hrs min. MIL-HDBK-217F (25℃)
Dimension460*211*83.5mm (L*W*H)
Packing10Kg; 1pcs/10.1Kg/0.85CUFT

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.