Masibus 85XX+ Multi Channel Universal Scanner
- Brand
- Masibus
- Model number
- 85XX+
- Category
- Process Indicators & Scanners
Masibus 85XX+ multi channel universal scanner: input Thermocouple, RTD, Voltage, Current, output 0/4 to 20 mA (Isolated). For substation monitoring, motor/generator monitoring and protection.
Price and availability on request
Key features
- Compact and Rugged
- Alpha-Numeric display for programmable tag no / Engg unit
- EMI/EMC Type test qualified & CE Marked
- 8 Channel Universal Analog Input Module
- 16 Channel Digital Input Module
- 4/ 8 Relay Output Module
- 24 Open Collector Output Module
- Analog Output
- Fast sampling and generation of Alarm/Trip
- User free mapping of Relay to Channels
- Comprehensive alarm/trip logic
- 2X RS485 Serial port
- 1X Ethernet port
- 1X USB port
- 1X Profibus-DP port
Specifications
| No of AI Modules | 1 (8 ch), 2 (16 ch) or 3 (24 ch) |
|---|---|
| Input Type | Thermocouple, RTD, Voltage, Current |
| Input Range | Refer Table -1 |
| ADC Resolution | 17 bits |
| Display Resolution | 0.1 / 1.0 °C |
| Sampling Rate | T/C & Voltage/Current: 50mSec/Channels RTD: 100mSec/Channels |
| Display Scan Rate | 1 to 99 Sec (Programmable) |
| CJC | Auto/ Manual/ External for T/C type |
| CJC Error | ±2°C (0 to 55°C) |
| Sensor open | All inputs except 0-5V, 0-10V DC |
| Sensor Burnout current | 0.4uA |
| RTD excitation current | 250uA (Approx) |
| NMRR | > 40dB |
| CMRR | > 120dB |
| Temp-co | < 100ppm/°C |
| Input Impedance | > 1MΩ |
| Max Voltage | 20V DC |
| Connector Type | 24 pin Rectangular connector/25 pin D sub Connector |
| PV Value Format for Modbus | Integer/Swap Float |
| Channel to Channel Islolation for Isolated AI Card option | 125VAC/300VDC |
| No of DI modules | 1 (16 ch) |
|---|---|
| Response time | 50mSec |
| Rated Input Voltage | 24 V DC |
| Input On Voltage | ≥15 V DC |
| Input Off Voltage | ≤5 V DC |
| (At Rated Input Voltage) | Approx 3mA/ Channel |
|---|---|
| Maximum Allowable Input Voltage | 30 V DC |
| Channel number | 2-Digit, 0.56", Green seven segment LED |
|---|---|
| Process Value Engineering Unit | 4-Digit, 0.56", Red seven segment LED 6-Digit, 0.3", Orange Alphanumeric LED |
| Status LEDs | Manual, Run, Flt, Tx/Rx, Relay status Alarm/Control Status per channel |
| Keys | 2 X 4 for Configuration, Operation and Calibration |
| Relays | RL: 8 Nos per card RL4: 4 Nos per card RL8: 8 Nos per card |
|---|---|
| RL Module | RL (Form A): C- NO or C-NC (Jumper Selectable) |
| RL4 / RL8 Module | RL4 (Form C): C-NO-NC RL8 (Form C): C-NO-NC |
| Rating | 2A @ 250V AC / 30V DC |
| Connector Type | 25 D-Sub |
| OC Outputs | 24 |
|---|---|
| Rating | 100mA@30V DC |
| OC1 Module | Common pin: Ground only (O/P Logic Isolated) |
| OC2 Module | Common pin: +5V@1A/Ground, jumper selectable for Internal/External Relay drive (O/P Logic non-Isolated) *Default jumper set for Ground |
| Connector Type | 25 D-Sub |
| Number of outputs | Max upto 8 nos per card (Value: Min, Max, Avg) |
|---|---|
| Output signal | 0/4 to 20 mA (Isolated) |
| Load Resistance | 500Ω max |
| Output accuracy | ± 0.25 % of span |
| Protocol | Modbus-RTU Slave |
|---|---|
| Baud Rate | 9600, 19200, 57600 bps |
| Parity | Odd, Even, None |
| Stop Bit | 1, 2 |
| Connector | 2 pin, plug-in terminals |
| Protocol | Modbus - TCP/IP(Modnet) Slave |
|---|---|
| Baud Rate | 10 Mbps Connector RJ45 |
| Protocol | Profibus DP V0 Slave |
|---|---|
| Max. In/Out Bytes | 244 IN / 244 OUT Bytes |
| Baud Rate | 1200 to 12 Mbps Auto Detecting |
| Connector | 9-Pin D-type Female |
| Device Type | Profinet I/O Device |
|---|---|
| Communication Protocol | Profinet |
| Network Topology | MRP (Media Redundancy Protocol), STAR, LINE |
| Network Port | 2 Nos (RJ-45) |
| Max . II/nP/,O Ou/tp B Dyatetas | 256 IN / 256 OUT Bytes* |
| Network Speed | 10/100 Mbps, Auto-negotiation & Auto-crossover |
| Data Transport Layer | Ethernet II, IEEE 802.3 |
| Configuration File | GSDML available |
| MCoanxf oI/rPm, Oan/pc eD Caltaass | Class C |
| Device Type | EtherNet/IP Adapter (Slave) |
|---|---|
| Communication Protocol | EtherNet/IP |
| Network Topology | DLR (Device Level Ring), TREE, LINE |
| Network Port | 2 Nos (RJ-45) |
| Max . II/nP/,O Ou/tp B Dyatetas | 504 IN / 504 OUT Bytes* |
| Network Speed | 10/100 Mbps, Auto-negotiation & Auto-crossover |
| Data Transport Layer | Ethernet II, IEEE 802.3 |
| No of port | 1 no max |
| Standard | 2.0 |
| Data format | Excel |
| Max. USB pen drive size | Upto 16 GB supported |
| Memory Size | 25MB (Periodic), 7MB (Event) |
|---|---|
| Data retrieval | via mSCAN+ Software |
| Min Periodic Log Time | 1 min |
| No of Records | 101888 X / 256 (2XNo. of Ch) +12 |
| Voltage | 85-265 V AC, 50/60 Hz/ 100-295 V DC 18 - 36V DC (Optional) |
|---|
| Size (in mm) | 144 (H) X 72 (W) X 165 (D) |
|---|---|
| Panel Cutout (in mm) | 137 (H) X 68.5 (W) |
| Depth behind Panel (in mm) | 155 / 203 (with cable connector) |
| Mounting | Panel Mount (Standard) |
| Weight | 1.25 Kg |
| Enclosure Material | Extruded Aluminum |
| Protection | IP20 (Overall, except terminals), IP55 (Front Fascia) Table 1: Display Range |
| Input Type | Ranges |
| RTD | Pt100 / -199.9 °C to 850.0 °C; Cu53 -210.0 °C to 210.0 °C; NI-120 -70.0 °C to 210.0 °C |
| Voltage/Current | 0/4 -20mA (Ext. 250Ω) 0/1-5V -10 to 20 mV DC -1999 to 99 0 - 100 mV DC 0 - 10 V DC |
| Applications | Substation Monitoring, Motor/Generator Monitoring and Protection, Transformer monitoring and protection, Compressor/Pump/DG set monitoring, Asset Monitoring, As a Serial/Ethernet RTU, Remote I/O module, Multi Point On/Off control |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.