Masibus 40005E Bar Graph Indicator

Brand
Masibus
Model number
40005E

Masibus 40005E bar graph indicator: output 0/4 to 20 mA (Isolated). For monitoring of level, vibration, flow, etc, alarm/trip unit.

Price and availability on request

Request a quote

Sent with the product details: Masibus 40005E Bar Graph Indicator.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Micro controller based
  • Full 4 digit numeric & 101 segment bar display
  • Universal Input
  • Square root extractor
  • Fully configurable & programmable by front keypad or PC based mbGRAPH Configuration Software
  • Digital calibration
  • Watchdog output
  • Power Supply, Input & Output Isolated for 1500VAC
  • Built-in Transmitter Supply
  • Options : Analog output (Isolated) Redundant RS485 serial port 4 Relay Output
  • Analog output (Isolated)
  • Redundant RS485 serial port 4 Relay Output

Specifications

Input
No of Inputs1 or 2
Input Type & Measurement RangeRefer Table-1
ADC Resolution17 bits
Display Resolution0.1 / 1.0 °C
Sampling RateT/C & Voltage/Current: 50mSec/Ch RTD: 100mSec/Ch
CJCAutomatic for thermocouple input
CJC Error± 2 °C maximum
Sensor openAll inputs except 0-5V / 0-20 mA
Sensor Burnout current0.4µA
RTD Excitation current250µA (Approx.)
NMRR> 40dB
CMRR> 120dB
Temp-co< 100ppm/°C
Input Impedance> 1 MΩ
Max Input Voltage20VDC
Display & keys
Process Value display (one per channel)0.3", 4- digit 7- segment Red LED
Status indicating LEDRed LEDs Tx/Rx, Relay status
KeysUp/Down, MENU/ENTER, ESC
Bar Display (one per channel)
LED Bar101
Relay Output (Optional)
Relays4 Nos
Rating2A @ 250 V AC / 30V DC
Connector Type25 D-Sub
Analog Output (Optional)
No. of outputsOne per channel
Output Signal0/4 to 20 mA (Isolated)
Load Resistance500Ω or less
Output accuracy± 0.25 % of span
Interface2 Wire, EIA RS485
ProtocolModbus-RTU Slave
Baud Rate9600 or 19200
Specifications
Transmitter Power Supply24 VDC ± 5% @ 30 mA (one per channel)
Power Supply
Voltage85-265 V AC, 50/60 Hz/ 100-295 V DC 18 - 36V DC (Optional)
Power Consumption16VA (Max) [85-265V AC] 8VA (Max) [18-36VDC]
Physical
Dimensions (mm)144(H) x 72(W) x 165(D)
Front Bezel (mm)144(H) x 72(W)
P anel Cutout (mm)137(H) x 68.5(W)
Depth behind Panel (mm)155
MountingPanel Mount
Weight1.25 Kg
Enclosure MaterialE xtruded Aluminum
ProtectionIP20 (Overall) IP54 (Front fascia)
Environmental
Operating Temperature-10 to 55 °C
Storage Temperature0 to 80 °C
Humidity20 to 95% RH non condensing Table 1: Display Range
RTDPt-100 / -199.9 to 850.0 °C; Cu-53 -210.0 °C to 210.0 °C; NI-120 -70.0 °C to 210.0 °C
Product
ApplicationsMonitoring of Level, Vibration, Flow, etc, Alarm/Trip Unit, On/off Controller, Digital Switch, Gas Detection, Marine-Utility Monitoring on Ships
IndustriesPower Plant

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.