Lutron PIR-9959A IR Temperature Controller / Monitor
- Brand
- Lutron
- Model number
- PIR-9959A
- Category
- Temperature Controllers
Panel controller for 4 to 20 mA IR temperature transmitters such as the TR-IR420, displaying 0 to 300 °C with two relay outputs.
Price and availability on request
Key features
- Input: 4-20 mA DC, 4 mA = 0.0 °C or 4 mA = 32 °F 20 mA = 300.0 °C or 20 mA = 572 °F
- User can default the Temp. unit to °C or °F.
- User can default the resolution of Temp. value to 0.1 degree or 1 degree.
- When PIR-9959 cooperate LUTRON's 4 to 20 mA IR Temp. transmitters (TR-Ir420), whole system will become the high performance Controller/Alarm/Indicator of no contact IR Temp. measurement system.
- Easy to adjust the function factors by push button on the front panel.
- Control output: 2 points (COM, NO).
- Alarm output: 2 points (COM, NO).
- Control Relay will make action when the reading value reach to control value.
- Hysteresis value setting for control and alarm function.
- Large red LED display, high brightness and easy to read.
- Microprocessor circuit ensures high accuracy and provides special functions and features.
- DC 24V power supply output, used for the power supply external IR Temp. transmitter.
- RS232/USB computer interface.
- Power: 90 ACV - 260 ACV, 50/60 Hz.
- Standard 96 X 48 mm DIN case.
- Optional data acquisition software.
Specifications
| Circuit | Custom chip of microprocessor LSI circuit. |
|---|---|
| Display | * 4 digits red LED, 14 mm ( 0.55 inch ) digit height; * 4 indicators : PV ( process value ) indicator; SV ( set value ) indicator; Control out indicator; Alarm out indicator; * User can set the Temp. unit to or °C °F with default.; * User can set the Temp. value to 0.1degree or 1 degree with default. |
| Measurement | 0.1 °C resolution : 0.0 to 300.0 °C; 1 °Cresolution : 0 to 300 °C; 0.1°F resolution : 32.0 to 572.0 °F; 1 °F resolution : 32 to 572 °F |
| Input Signal CH1, CH2, CH3 | Linear, 4 to 20 mA; * It should cooperate the LUTRON's optional IR Temp. transmitter, TR-IR2W |
| Datalogger Sampling Time | Approx. 1 second. |
| Data Output | RS 232 PC serial interface. |
| Operating temperature | 0 to 50°C |
| Operating humidity | Less than 80% R.H. |
| Power Supply | 90 to 260 ACV, 50/60 Hz. |
| Power Consumption | Approx. 9.2 VA/AC 110V.; Approx. 12.0 VA/AC 220V. |
| Weight | 384 g/ 0.84 LB. |
| Dimension | DIN size : 96 x 48 mm.; Panel cut size : 92 mm x 46 mm.; Depth : 110 mm. |
| Setting value | * Display resolution setting : 1 degree or 0.1 degree; * Low limit of range adjustment : 4 mA = 0.0 for.; 4 mA = 32.0 for.; * High limit of range adjustment : 20 mA = 400.0 for.; 20 mA = 752.0 for.; * Alarm value adjustment : High Alarm or Low alarm.; * Control value adjustment; High control or Low control.; * Control hysteresis value setting. |
| Relay outputs | Control Relay will make action when the reading value; reach to control value. |
| Supplied with | Instruction manual : 1 PC; Case holder with screw : 2 PCs |
|---|---|
| Optional | * IR Temp. Transmitter, TR-IR420.; * Data Acquisition software, SW-U801-WIN.; * RS232 cable, UPCB-02.; * USB cable, USB-01.; * SD card data logger, DL-9602SD. |
| Span | ±(0.15% + 2d) F.S. @ 23 ± 5°C |
|---|
| Max Load | 0.5 ACA/250 ACV, 0.5 DCA/24 DCV (Do not exceed 0.5 A) |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.