Lutron PHT-3109 Humidity / Temperature Controller / Monitor
- Brand
- Lutron
- Model number
- PHT-3109
- Category
- Process Indicators & Scanners
Panel controller and monitor for humidity (10 to 95 %RH) and temperature, with separate humidity and temperature relays, offset and hysteresis settings.
Price and availability on request
Key features
- Professional Humidity measurement monitor and controller.
- Build in humidity control relay and the Temp. control relay.
- Relay will be make action (On/Off) when the reading value reach high limit or low limit value.
- Offset value setting.
- Hysteresis value setting for high and low alarm.
- °C,°F temp. unit setting with default.
- High precision humidity sensor with fast response time and high accuracy.
- Large red LED display, high brightness and easy to read.
- RS232 computer interface, send out the humidity and the temperature data at the same time.
- Optional data acquisition software.
- Optional GSM controller.
- Microprocessor circuit ensures high accuracy and provides special functions and features.
- Standard 96 X 48 mm DIN case.
Specifications
| Circuit | Custom chip of microprocessor LSI circuit. |
|---|---|
| Display | 4 digits red LED, digit size : 14 mm. |
| Measurement | Humidity; Temperature |
| Datalogger Sampling Time | Approx. 1 second. |
| Data Output | RS 232 PC serial interface. |
| Operating temperature | 0 to 50°C.; * Meter |
| Operating humidity | Less than 80% R.H.; * Meter |
| Power Supply | 90 to 260 ACV, 50/60 Hz. |
| Power Consumption | Approx. 4.7 VA/AC 110V.; Approx. 5.3 VA/AC 220V. |
| Weight | 384 g/ 0.84 LB. * Including probe. |
| Dimension | DIN size : 96 x 48 mm.; Depth : 110 mm. |
| Setting value | High limit value setting.; Low limit value setting.; Hysteresis value setting.; Offset value setting.; * Setting for Humidity and Temp. |
| Relay outputs | Number : 2 relays; Function; Relay 1 : Humidity control relay.; Relay 2 : Temperature control relay.; Max load : 1 ACA/250 ACV; 1 DCA/24 DCV |
| Supplied with | Instruction manual : 1 PC; Humidity/Temp. probe : 1 PC; Case holder with screw : 2 PCs; Probe fix holder : 1 PC |
|---|---|
| Optional | * Data Acquisition software, SW-U801-WIN.; * RS232 cable, UPCB-02.; * USB cable, USB-01.; * GSM controller, GSM-889.; * Interface cable ( cable between meter to GSM-889 ), GMCB-89. |
| Range | 10% to 95% RH |
|---|---|
| Resolution | 0.1% RH |
| Accuracy | ±(3% reading + 1% RH) for ≥70% RH, ±3% RH for <70% RH |
| Range | 0 to 50°C (32 to 122°F) |
| Resolution | 0.1°C/0.1°F |
| Accuracy | ±0.8°C/±1.5°F |
| External DC | 12V, 50 mA max |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.