Hioki PW3365-20 Clamp On Power Logger

Brand
Hioki
Model number
PW3365-20

Clamp-on power logger (English model) that takes voltage from over the cable insulation with no risk of short circuit: single to three-phase 4-wire, 90 V to 520 V, harmonics to the 13th; main unit only.

Price and availability on request

Request a quote

Sent with the product details: Hioki PW3365-20 Clamp On Power Logger.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Measure voltage from the top of the cable with zero risk of short circuit
  • Supports single to three-phase, 4-wire circuits
  • Measure between 90 V to 520 V
  • Display harmonics up to the 13th order
  • Slim, compact design that can be placed anywhere
  • Store months of data on SD cards
  • QUICK SET function guides you in making the right connections

Specifications

Specifications
Measurement line & number of circuits50/60 Hz, Single phase 2 wires (1/2/3 circuits), Single phase 3 wires (1 circuit), Three phases 3 wires (1 circuit), Three phases 4 wires (1 circuit), Current only: 1 to 3 channels
Measurement itemsVoltage RMS, current RMS, voltage fundamental wave value, current fundamental wave value, voltage fundamental wave phase angle, current fundamental wave phase angle, frequency (U1), voltage waveform peak (absolute value), current waveform peak (absolute value), active power, reactive power, apparent power, power factor (with lag/lead display) or displacement power factor (with lag/lead display), active energy (consumption, regeneration), reactive energy (lag, lead), energy cost display, active p
Voltage ranges400 V AC (Effective measurement range: 90.0 V to 520.0 V)
HarmonicHarmonic voltage, harmonic current, voltage total harmonic distortion (THD-F or THD-R), current total harmonic distortion (THD-F or TDH-R), up to 13th order
Current ranges500.00 mA to 5.0000 kA AC (depends on current sensor in use), 50.000 mA to 5.0000 A AC (Leak clamp on sensor only)
Power ranges200.00 W to 6.0000 MW (depends on voltage/current combination and measured line type)
Basic accuracyVoltage : ±1.5% rdg. ±0.2% f.s(combined accuracy with PW3365-20 + PW9020) Current : ±0.3% rdg. ±0.1% f.s. + clamp sensor accuracy Active power : ±2.0% rdg. ±0.3% f.s. + clamp sensor accuracy (at power factor = 1)
Display update rate0.5 sec (except when accessing SD card or internal memory, or during LAN/USB communication)
Save destinationSD/SDHC Memory card, or internal memory at real time
Data save interval1 sec to 30 sec, 1 minute to 60 minutes, 14 selections
Save itemsMeasurement value save: Average only / Average, Maximum, Minimum value Screen copy: BMP form (saved every 5 min. at minimum interval time) Waveform save: Binary waveform data
InterfacesSD/SDHC memory card, LAN 100BASE-TX: HTTP server function, remote settings via communication program, data download, USB 2.0: When connected to a PC, the SD Card and internal memory are recognized as removable storage devices, remote settings via communication program, data download
FunctionsConnection check, Quick Set navigation guide, clock
Power supplyAC adapter Z1008: (100 to 240 V AC, 50 Hz/60 Hz), 45 VA (including AC adapter) Battery pack 9459: (Max. rated power 5 VA, charging time 6 hr 10 m), 3 hours of continuous use (with backlight off)
Dimensions and mass180 mm (7.09 in.)W × 100 mm (3.94 in.)H × 48 mm (1.89 in.)D, 540 g (19 oz.) without PW9002 180 mm (7.09 in.)W × 100 mm (3.94 in.)H × 68 mm (2.68 in.)D, 820 g (28.9 oz.) with PW9002
Supplied with
ContentsSafety Voltage Sensor PW9020 ×1 set, AC adapter Z1008 ×1, USB cable L1003 ×1, Instruction manual ×1, Measurement guide ×1, Color clip (red, yellow, blue and white each 4), Spiral tubes in black (cord bundling for current sensors and voltage sensors) ×10
PW9020 voltage sensor
Compatible conductor typesInsulated wires* In door PVC or metal parts *Shielded wires cannot be measured. The product may not be able to accurately measure multi-core cables or cables that have thick insulation.
Compatible conductor diametersFinished outer diameter φ6mm to φ30mm
Effective measurement range90 V rms to 520 V rms
Cord length3m (9.84 ft)
Ordering
Order codePW3365-20 (English model, main unit only)
NoteClamp On Power Logger PW3365 by itself does not support current and power measurements. Current and power measurements require clamp on sensors, sold separately. Use only Hioki SD cards guaranteed to work for saving measurement data (options, sold separately).

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.