Delta DRS-12V50W1NZ 12V 4A 48W DIN Rail Power Supply, SYNC Series
- Brand
- Delta
- Model number
- DRS-12V50W1NZ
- Category
- DIN-Rail Power Supplies
SYNC DIN rail power supply with 12V 4A output (48W) from 85-264Vac or 120-375Vdc. Plastic case and convection cooling, operating -20 to +70 °C. With NEC Class 2 rating.
Price and availability on request
Key features
- Ultra-compact size and galvanic isolation up to 3.0KVac between input to output and input to ground
- Universal AC input voltage and full power from -10°C to +55°C operation
- Up to 89.0% efficiency
- Low earth leakage current < 0.5mA @ 264Vac
- Built-in DC OK relay contact option available
- Extreme low temperature cold start at -40°C
- NEC Class 2 / Limited Power Source (LPS) certified
- Certified according to IEC/EN/UL 62368-1
Specifications
| Series | SYNC Series |
|---|---|
| Mounting | DIN rail |
| Output Current | 4A |
|---|---|
| Output Voltage | 12V |
| Output Voltage Adjustment Range | 12-15Vdc |
| Output Power | 48W |
| Line Regulation | < 0.5% (@ 85-264Vac, 100% load) |
| Load Regulation | < 1.0% (@ 85-264Vac, 0-100% load) |
| PARD | < 50mVpp @ > 0°C to 70°C / < 100mVpp @ 0°C to -20°C |
| Start-up Time | < 2,000ms @ 115Vac (100% load) / < 1,000ms @ 230Vac (100% load) |
| Hold-up Time | > 20ms @ 115Vac (100% load) / > 100ms @ 230Vac (100% load) |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 5% @ 85-264Vac input, 0-100% load (Slew Rate: 0.1A/μs, 50% duty cycle @ 5Hz to 1KHz) |
| Start-up with Capacitive Loads | 3,000μF Max |
| Nominal Input Voltage | 100-240Vac |
|---|---|
| Input Voltage Range | 85-264Vac |
| Nominal Input Frequency | 50-60Hz |
| Input Frequency Range | 47-63Hz |
| DC Input Voltage Range | 120-375Vdc |
| Input Current | < 0.9A@115Vac, < 0.55A @ 230Vac |
| Efficiency at 100% load | > 88%@ 115Vac, > 89% @ 230Vac |
| Inrush Current | < 25A @ 115Vac, < 50A @ 230Vac |
| Leakage Current | < 0.5 mA @ 264 Vac |
| Power Dissipation | 0% load: < 0.3W @ 115Vac, < 0.4W@ 230Vac / 100% load: < 6W @ 115Vac & 230Vac |
| Case Chassis / Cover | Plastic |
|---|---|
| Indicator | Green LED (DC OK) |
| Cooling System | Convection |
| Unit Weight | 0.18 kg (0.40 lb) |
| Dimensions | 75 x 30 x 89.5 mm / 2.95” x 1.18” x 3.52” |
| Vibration (Operating) | IEC 60068-2-6, Sine Wave: 10-500Hz; 2G peak; displacement of 0.35mm; 1 octave per min; 60 min per axis for all X, Y, Z directions |
|---|---|
| Shock Test (Operating) | IEC 60068-2-27, Half Sine Wave: 10G for a duration of 11ms; 1 time in X axis |
| Operating Temperature | -20°C to +70°C (Cold start at -40°C@ 40% load) |
| Storage Temperature | -40°C to +85°C |
| Power De-rating | -10°C to -20°C de-rate power by 2% / °C / > 55°C de-rate power by 3.33% / °C |
| Operating Humidity | 5 to 95% RH (Non-Condensing) |
| Shock Test (Non-Operating) | IEC60068-2-27, Half Sine Wave: 50G for a duration of 11ms; 3 times per direction, 9 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, Random: 5-500Hz; 2.09Grms, 20 min per axis for all X, Y, Z directions |
| Pollution Degree | 2 |
| Overvoltage | < 18.7V, SELV Output, Latch Mode |
|---|---|
| Overload / Overcurrent | 105~120% of rated load current, Foldback Mode (continuous current, voltage drops), Auto-recovery when the fault is removed |
| Over Temperature | < 75°C Surrounding Air Temperature @ 100% load, Latch Mode |
| Short Circuit | Hiccup Mode, Non-Latching (Auto-recovery when the fault is removed) |
| Degree of Protection | IP20 |
| Protection Against Shock | Class I with PE connection |
| MTBF | > 700,000 hrs. as per Telcordia SR-332 / I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 35°C / 230,000 hrs. as per MIL-HDBK-217F / I/P: 115Vac & 230Vac,O/P: 100% load, Ta: 25°C |
|---|---|
| Expected Cap Life Time | 10 years (115ac & 230Vac, 50% load @ 40°C) |
| Electrical Safety | TUV Bauart: EN 62368-1 / UL/cUL recognized: UL 60950-1, UL 62368-1, CSA C22.2 No. 60950-1 (File No. E191395) / CB Scheme: IEC 60950-1, IEC 62368-1, Limited Power Source (LPS) |
|---|---|
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| Galvanic Isolation | Input to Output: 3.0 KVac / Input to Ground: 3.0 KVac / Output to Ground: 0.5 KVac |
| Industrial Control Equipment | UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315335) |
| Safety Entry Low Voltage | SELV (IEC 60950) |
| Material and Parts | RoHS Directive 2011/65/EU Compliant |
| UKCA | In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and / The Electromagnetic Compatibility Regulations 2016 No. 1091 |
| Emission | Generic Standards: EN/BS EN 61000-6-3, EN/BS EN 61000-6-4, / CISPR 32, EN/BS EN 55032, EN/BS EN 55011, FCC Title 47: Class B |
|---|---|
| Immunity | Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-1, EN/BS EN 61000-6-2 |
| Harmonic Current Emissions | IEC/EN/BS EN 61000-3-2, Class A |
| Voltage Fluctuation and Flicker | IEC/EN/BS EN 61000-3-3 |
| Component Power Supply for General Use | EN 61204-3 |
| Tags | NEC Class 2 |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.