Delta DRP048V120W1BN 48V 2.5A 120W DIN Rail Power Supply, CliQ II Series

Brand
Delta
Model number
DRP048V120W1BN

CliQ II DIN rail power supply with 48V 2.5A output (120W) from 85-264Vac or 120-375Vdc. Aluminium case and convection cooling, operating -25 to +80 °C. With power boost and conformal-coated boards.

Price and availability on request

Request a quote

Sent with the product details: Delta DRP048V120W1BN 48V 2.5A 120W DIN Rail Power Supply, CliQ II Series.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Universal AC input voltage range
  • Power will not de-rate for the entire input voltage range
  • Power Boost of 150% for 5 seconds
  • Full corrosion resistant aluminium casing
  • Conforms to harmonic current IEC/EN 61000-3-2, Class A
  • Extreme low temperature cold start at -40°C
  • Conformal coating on PCBAs to protect against common dust and chemical pollutants
  • Hazardous Locations approval for ATEX and Class I, Div 2 (DRP048V120W1BA)
  • Certified according to IEC/EN/UL 62368-1

Specifications

Product
SeriesCliQ II Series
MountingDIN rail
Output
Output Current2.5A
Output Voltage48V
Output Voltage Adjustment Range48-56Vdc
Output Power120W
Line Regulation< 0.5% (@ 85-264Vac input, 100% load)
Load Regulation< 1.0% (@ 85-264Vac input, 0-100% load)
PARD< 200mVpp
Start-up Time< 2,000ms @ nominal input (100% load)
Hold-up Time> 20ms @ 115Vac, / > 50ms @ 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)± 2% @ 85-264Vac input, 0-100% load / (Slew Rate: 0.1A/μs, 50% duty cycle @ 5Hz)
Start-up with Capacitive Loads6,500μF Max
Rise Time< 200ms @ nominal input (100% load)
Input
Nominal Input Voltage100-240Vac
Input Voltage Range85-264Vac
Nominal Input Frequency50-60Hz
Input Frequency Range47-63Hz
DC Input Voltage Range120-375Vdc
Input Current< 2.20A @ 115Vac, / < 1.10A @ 230Vac
Efficiency at 100% load> 90.0% @ 115Vac, / > 91.0% @ 230Vac
Inrush Current< 35A @ 115Vac & 230Vac
Power Factor at 100% load> 0.99 @ 115Vac, / > 0.93 @ 230Vac
Leakage Current< 1mA @ 240Vac
Power Dissipation0% load: < 2.5W @ 115Vac, < 3.5W @ 230Vac / 100% load: < 13.2W @ 115Vac, < 11.8W @ 230Vac
Mechanical
Case Chassis / CoverAluminium
IndicatorGreen LED (DC OK)
Cooling SystemConvection
Input Terminal3 Pins (Rated 300V/15A)
Output Terminal4 Pins (Rated 300V/15A)
Noise Sound Pressure Level (SPL)< 40dBA
Mounting RailStandard TS35 DIN Rail in accordance with EN 60715
WireInput / Output: AWG 20-12
Unit Weight0.72 kg (1.59 lb)
Dimensions121 x 50 x 123.1 mm / 4.76” x 1.97” x 4.85”
Environment
Operating Temperature-25°C to +80°C (Cold Start at -40°C)
Storage Temperature-40°C to +85°C
Power De-ratingVertical: > 50°C de-rate power by 2.5% / °C / Horizontal: > 50°C de-rate power by 2.5% / °C, > 70°C de-rate power by 3.5% / °C
Operating Humidity5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)IEC60068-2-27, 30G (300m/S²) for a duration of 18ms, 1 time per direction, 2 times in total
Vibration (Non-Operating)IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak); 60 min per axis / for all X, Y, Z direction
Operating Altitude0 to 2,500 Meters (8,200 ft.)
Pollution Degree2
Bump Test (Operating)IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
Over Voltage CategoryIII / According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part)
Protections
Overvoltage< 57V, SELV Output, Hiccup Mode, Non-Latching (Auto-Recovery)
Overload / Overcurrent> 150% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery)
Over Temperature< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
Short CircuitHiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of ProtectionIP20
Protection Against ShockClass I with Primary Earth connection
Reliability
MTBF> 800,000 hrs. as per Telcordia SR-332 (I/P: 115Vac, O/P: 100% load, Ta: 25°C)
Expected Cap Life Time10 years (115Vac & 230Vac, 50% load @ 40°C)
Safety
Electrical SafetySIQ Bauart: EN 62368-1 / UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) / CB scheme: IEC 60950-1, IEC 62368-1 / UKCA: BS EN 62368-1 / CCC: GB9254, GB17625.1 and GB4943.1 (仅适用于海拔 2000m 以下地区安全使用)
CEIn conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU / For DRP048V120W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU
Galvanic IsolationInput to Output 4.0 KVac / Input to Ground 1.5 KVac / Output to Ground 1.5 KVac
Industrial Control EquipmentUL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355) / CSA: CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX(For DRP048V120W1BA) / cCSAus: CSA C22.2 No. 213-M1987 and ANSI / ISA 12.12.01:2011 [Class I, Division 2, Group A, B, C, D T4, Ta= -25°C to +80°C (> +50°C derating)] / / ATEX: EN 60079-0:2009, EN 60079-15:2010 [II 3G Ex nA nC IIC T4 Gc, Ta= -25°C to +80°C (> +50°C derating)] / Certificate No. EPS 12 ATEX 1 491 X
Electrical Equipments of MachinesEN/BS EN 60204-1 (over voltage category III)
Electrical Equipment for Use in Electrical Power InstallationsIEC/EN/BS EN 62477-1 / IEC 62103
Safety Entry Low VoltageSELV (IEC 60950-1)
UKCAIn conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
EMC
Emission(CE & RE) / Generic Standards: CISPR 32, EN/BS EN 55032, CISPR 11, EN/BS EN 55011, FCC Title 47: Class B
ImmunityGeneric Standards: EN/BS EN 55024, EN/BS EN 61000-6-1, EN/BS EN 61000-6-2
Harmonic Current EmissionsIEC/EN/BS EN 61000-3-2, Class A
Voltage Fluctuation and FlickerIEC/EN/BS EN 61000-3-3
Component Power Supply for General UseEN/BS EN 61204-3
Other
TagsATEX, Class I Div 2, Conformal Coating

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.