Delta DRP024V240W3BN 24V 10A 240W 3-Phase DIN Rail Power Supply, CliQ II Series
- Brand
- Delta
- Model number
- DRP024V240W3BN
- Category
- DIN-Rail Power Supplies
CliQ II DIN rail power supply with 24V 10A output (240W) from 3 x 320-600Vac or 450-800Vdc. Aluminium case and convection cooling, operating -25 to +80 °C. With power boost and conformal-coated boards.
Price and availability on request
Key features
- Universal AC input voltage range
- Power will not de-rate for the entire input voltage range
- Power Boost of 150% for 5 seconds
- Full corrosion resistant aluminium casing
- Conforms to harmonic current IEC/EN 61000-3-2, Class A
- Extreme low temperature cold start at -40°C
- Conformal coating on PCBAs to protect against common dust and chemical pollutants
- Hazardous Locations approval for ATEX and Class I, Div 2 (DRP024V240W3BA)
- Certified according to IEC/EN/UL 62368-1
Specifications
| Series | CliQ II Series |
|---|---|
| Mounting | DIN rail |
| Output Current | 10A |
|---|---|
| Output Voltage | 24V |
| Output Voltage Adjustment Range | 24-28Vdc |
| Output Power | 240W |
| Line Regulation | < 0.5% (@ 3 x 320-600Vac input, 100% load) |
| Load Regulation | < 1.0% (@ 3 x 320-600Vac input, 0-100% load) |
| PARD | < 150mVpp |
| Start-up Time | < 1,000ms @ nominal input (100% load) |
| Hold-up Time | > 20ms @ 3 x 400Vac, / > 40ms @ 3 x 500Vac (100% load) |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 5% @ 3 x 320-600Vac input, 0-100% load / (Slew Rate: 0.1A/μs, 50% duty cycle @ 5Hz to 1KHz) |
| Start-up with Capacitive Loads | 10,000µF Max |
| Rise Time | < 100ms @ nominal input (100% load) |
| Nominal Input Voltage | 3 x 400-500Vac |
|---|---|
| Input Voltage Range | 3 x 320-600Vac |
| Nominal Input Frequency | 50-60Hz |
| Input Frequency Range | 47-63Hz |
| DC Input Voltage Range | 450-800Vdc |
| Input Current | < 0.75A @ 3 x 400Vac, / < 0.65A @ 3 x 500Vac |
| Efficiency at 100% load | > 91.0% @ 3 x 400Vac & 3 x 500Vac |
| Inrush Current | < 40A @ 3 x 400Vac & 3 x 500Vac |
| Leakage Current | < 3.5mA @ 500Vac |
| Power Dissipation | 0% load: < 6.5W @ 3 x 400Vac & 3 x 500Vac / 100% load: < 23.0W @ 3 x 400Vac & 3 x 500Vac |
| Case Chassis / Cover | Aluminium |
|---|---|
| Indicator | Green LED (DC OK) |
| Cooling System | Convection |
| Input Terminal | 4 Pins (Rated 600V/35A) |
| Output Terminal | 4 Pins (Rated 300V/28A) |
| Noise Sound Pressure Level (SPL) | < 40dBA |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Wire | Input: AWG 18-12 / Output: AWG 16-12 |
| Unit Weight | 0.89 kg (1.96 lb) |
| Dimensions | 121 x 70 x 117.3 mm / 4.76” x 2.76” x 4.62” |
| Operating Temperature | -25°C to +80°C |
|---|---|
| Storage Temperature | -40°C to +85°C |
| Power De-rating | Vertical: > 50°C de-rate power by 2.5% / °C, > 70°C de-rate power by 5% / °C / Horizontal: > 40°C de-rate power by 2.5% / °C, > 60°C de-rate power by 5% / °C |
| Operating Humidity | 0 to 95% RH (Non-Condensing) |
| Shock Test (Non-Operating) | IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms, 1 time per direction, 2 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak); 60 min per axis for all X, Y, Z direction |
| Operating Altitude | 0 to 2,500 Meters (8,200 ft.) for ITE application / 0 to 2,000 Meters (6,560 ft.) for Industrial application |
| Pollution Degree | 2 |
| Bump Test (Operating) | IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total |
| Over Voltage Category | IlI / According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part) |
| Overvoltage | 32V ±10%, SELV Output, Hiccup Mode, Non-Latching (Auto-Recovery) |
|---|---|
| Overload / Overcurrent | > 150% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery) |
| Over Temperature | < 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery) |
| Short Circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Degree of Protection | IP20 |
| Protection Against Shock | Class I with Primary Earth connection |
| MTBF | > 500,000 hrs. as per Telcordia SR-332 (I/P: 3 x 400Vac, O/P: 100% load, Ta: 25°C) |
|---|---|
| Expected Cap Life Time | 10 years (3 x 400Vac & 3 x 500Vac, 50% load @ 40°C) |
| Electrical Safety | SIQ Bauart: EN 62368-1 / UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) / CB scheme: IEC 60950-1, IEC 62368-1 / UKCA: BS EN 62368-1 / BIS: IS 13152-1 |
|---|---|
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU / For DRP024V240W3BA: / In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU |
| Galvanic Isolation | Input to Output 4.0KVac / Input to Ground 2.0KVac / Output to Ground 1.5KVac |
| Industrial Control Equipment | UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355) / CSA: CSA C22.2 No. 107.1-01 (File No. 181564) |
| Hazardous Location / ATEX | (For DRP024V240W3BA) / cCSAus: CSA C22.2 No. 213-M1987 and ANSI / ISA 12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4, Vertical: Ta = -25°C to +80°C, > +50°C derating, Horizontal: Ta = -25°C to +70°C, > +40°C derating)] / / ATEX: EN 60079-0:2012, EN 60079-15:2010 [II 3G Ex nA IIC T4 Gc, (Vertical: Ta = -25°C to +80°C, > +50°C derating, Horizontal: Ta = -25°C to +70°C, > +40°C derating)] / Certificate No. EPS 13 ATEX 1 575 X |
| Electrical Equipments of Machines | EN/BS EN 60204-1 (over voltage category III) |
| Electrical Equipment for Use in Electrical Power Installations | IEC/EN/BS EN 62477-1 / IEC 62103 |
| Safety Entry Low Voltage | SELV (IEC 60950-1) |
| UKCA | In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091 |
| Emission | (CE & RE) / Generic Standards: CISPR 32, EN/BS EN 55032, CISPR 11, EN/BS EN 55011, FCC Title 47: Class B |
|---|---|
| Immunity | Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2 |
| Harmonic Current Emissions | IEC/EN/BS EN 61000-3-2, Class A |
| Voltage Fluctuation and Flicker | IEC/EN/BS EN 61000-3-3 |
| Component Power Supply for General Use | EN/BS EN 61204-3 |
| Tags | 3 phase, ATEX, Class I Div 2, Conformal Coating |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.