LYTE DIN rail power supply with 24V 3.125A output (75W) from 85-264Vac or 120-375 Vdc. Plastic case and convection cooling, operating -20 to +70 °C. With a constant-current mode and SEMI F47 compliance.

Price and availability on request

Request a quote

Sent with the product details: Delta DRL-24V75W1AZR 24V 3.125A 75W DIN Rail Power Supply, LYTE Series.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Universal AC input voltage range
  • Built-in constant current circuit for reactive loads
  • Up to 89% efficiency
  • Full power from -10°C to +50°C @ 230Vac with -30°C Cold Start
  • Compliance to SEMI F47 @ 200Vac
  • Limited Power Source (LPS) certified

Specifications

Product
SeriesLYTE Series
MountingDIN rail
Output
Output Current3.125A
Output Voltage24V
Output Voltage Adjustment Range21.6-26Vdc
Output Power75W
Line Regulation< 0.5% (@ 85-264Vac, 100% load)
Load Regulation< 1% (0-100% load)
PARD< 120mVpp @ > -10°C to +70°C / < 360mVpp @ ≤ -10°C to -30°C
Start-up Time1200ms typ. @ 115Vac (100% load) / 1000ms typ. @ 230Vac (100% load)
Hold-up Time16ms typ. @ 115Vac (100% load) / 60ms typ. @ 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)± 10% @ 115Vac & 230Vac input, 0-50%, 50-100% load / (Slew Rate: 2.5A/μS, 50% duty cycle @ 100Hz & 1KHz)
Start-up with Capacitive Loads5,000µF Max
Rise Time30ms typ. @ nominal input (100% load)
Input
Nominal Input Voltage100-240Vac
Input Voltage Range85-264Vac
Nominal Input Frequency50-60Hz
Input Frequency Range47-63Hz
DC Input Voltage Range120-375 Vdc
Input Current1.4A typ. @ 115Vac, 0.9A typ. @ 230Vac
Efficiency at 100% load89% typ. @ 230Vac
Inrush Current50A typ. @ 230Vac
Leakage Current< 1mA @ 240Vac
Mechanical
Case Chassis / CoverPlastic
IndicatorGreen LED (DC OK)
Cooling SystemConvection
Unit Weight0.22 kg (0.49 lb)
Dimensions123.6 x 27 x 102 mm / 4.87” x 1.06” x 4.02”
Environment
Vibration (Operating)IEC 60068-2-6, Sine Wave: 10Hz to 500Hz @ 19.6m/s² (2G peak); displacement of 0.35mm; 10 min per cycle, 60 min for X direction
Shock Test (Operating)IEC 60068-2-27, Half Sine Wave: 10G for duration of 11ms; 1 time in X axis
Operating Temperature-20°C to +70°C (-30°C Cold Start)
Storage Temperature-40°C to +85°C
Power De-rating-10°C to -20°C de-rate power by 1% / °C / > 40°C de-rate power by 1.67% / °C @ 115Vac / > 50°C de-rate power by 2.5% / °C @ 230Vac / Input Voltage: < 100Vac de-rate power by 1.33% / Vac
Operating Humidity5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)IEC 60068-2-27, Half Sine Wave: 50G for duration of 11ms; 3 times per direction, 9 times in total
Vibration (Non-Operating)IEC 60068-2-6, Random: 5Hz to 500Hz; 2.09Grms; 20 min per axis for all X, Y, Z directions
Operating Altitude0 to 5,000 Meters (16,400 ft.)
Pollution Degree2
Over Voltage CategoryII
Protections
Overvoltage<33.6V, SELV Output, Latch Mode
Overload / Overcurrent105 - 133% of rated load current, Constant current limit, Auto-recovery
Over TemperatureLatch Mode
Short CircuitHiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of ProtectionIP20
Protection Against ShockClass I with Primary Earth connection
Reliability
MTBFTelcordia SR-332: > 700,000 hrs / I/P: 100Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time10 years (115Vac & 230Vac, 50% load @ 40°C)
Safety
Electrical SafetyCB scheme: IEC 62368-1, IEC 60950-1, IEC 61010-1 / TUV Bauart: EN 62368-1 / UL/cUL: UL 62368-1, UL 61010-1/-2-201 / BSMI: CNS14336-1 / EAC: TP TC 004/2011 / KC: K60950-1
CEIn conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
Galvanic IsolationInput to Output: 3.0KVac / Input to Ground: 2.0KVac / Output to Ground: 0.5KVac
UKCAIn conformance with Electrical Equipment (Safety) Regulations 2016 and Electromagnetic Compatibility Regulations 2016
EMC
Emission(CE & RE) / CISPR 32, EN/BS EN 55032, EN/BS EN 55011, AS/NZS CISPR32: Class B; GB9254.1 / Compliance with: EN/BS EN 61000-6-3
ImmunityEN/BS EN 55035, EN/BS EN 55024 Compliance with: EN/BS EN 61000-6-1
Harmonic Current EmissionsIEC/EN/BS EN 61000-3-2, Class A; GB17625.1
Voltage Fluctuation and FlickerIEC/EN/BS EN 61000-3-3
Component Power Supply for General UseEN/BS EN 61204-3

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.