Delta DRL-24V480W1AS 24V 20A 480W DIN Rail Power Supply, LYTE Series
- Brand
- Delta
- Model number
- DRL-24V480W1AS
- Category
- DIN-Rail Power Supplies
LYTE DIN rail power supply with 24V 20A output (480W) from 85-264Vac or 120-375Vdc. Aluminium and steel case and convection cooling, operating -20 to +70 °C. With a constant-current mode, SEMI F47 compliance and conformal-coated boards.
Price and availability on request
Key features
- Universal AC input voltage
- Built-in constant current circuit for reactive loads
- Up to 88.0% efficiency
- Full power from -20°C to +50°C operation at 230Vac @ 5000 meters or 16400 feet altitude
- Built-in DC OK relay contact option available
- Compliance to SEMI F47 @ 200Vac
- Conformal coating on PCBAs to protect against common dust and chemical pollutants
Specifications
| Series | LYTE Series |
|---|---|
| Mounting | DIN rail |
| Output Current | 20A |
|---|---|
| Output Voltage | 24V |
| Output Voltage Adjustment Range | 22-28Vdc |
| Output Power | 480W |
| Line Regulation | < 0.5% (@ 85-264Vac, 100% load) |
| Load Regulation | < 1.5% (0-100% load)@ > -10°C to +70°C / < 2.0% ( 0-100% load) @ ≤ -10°C to -20°C |
| PARD | < 120mVpp @ > -10°C to +70°C / < 240mVpp @ ≤ -10°C to -20°C |
| Start-up Time | 1000ms typ.@ 115Vac & 230Vac (100% load) |
| Hold-up Time | 10ms typ.@ 115Vac (100% load) / 16ms typ.@ 230Vac (100% load) |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 10% (2400mVpp) @ 85-264Vac input, 0-50% load, 50-100% load (Slew Rate: 0.1A/μs) |
| Start-up with Capacitive Loads | 8,000µF Max |
| Rise Time | 100ms typ. @ nominal input (100% load) |
| Nominal Input Voltage | 100-240Vac |
|---|---|
| Input Voltage Range | 85-264Vac |
| Nominal Input Frequency | 50-60Hz |
| Input Frequency Range | 47-63Hz |
| DC Input Voltage Range | 120-375Vdc |
| Input Current | 5.4A typ.@115Vac, 2.7A typ.@ 230Vac |
| Efficiency at 100% load | 85% typ. @ 115Vac, 88% typ. @ 230Vac |
| Inrush Current | 40A typ.@115Vac, 80A typ.@ 230Vac |
| Power Factor at 100% load | > 0.95 @ 115Vac & 230Vac |
| Leakage Current | < 1mA @ 264Vac |
| Power Dissipation | 0% load: 5W @ 115Vac 4W @ 230Vac / 100% load: 50W @ 115Vac 40W @ 230Vac |
| Case Chassis / Cover | SGCC / Aluminium |
|---|---|
| Indicator | Green LED (DC OK) |
| Cooling System | Convection |
| Input Terminal | 3 Pins (Rated 600V/35A) |
| Output Terminal | 6 Pins (Rated 300V/28A) |
| Signal Terminal | 6 Pins (Rated 300V/28A) |
| Noise Sound Pressure Level (SPL) | < 25dBA |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Wire | Input: AWG 16-12 / Output: AWG 16-14 (2 pieces of wire), AWG 12 / Signal: AWG 16-12 |
| Unit Weight | 1.30 kg (2.87 lb) |
| Dimensions | 123.6 x 85.5 x 128.5 mm / 4.87” x 3.37” x 5.06” |
| Vibration (Operating) | IEC 60068-2-6, Sine Wave: 10Hz to 500Hz @ 19.6m/s² (2G peak); displacement of 0.35mm; 10 min per cycle, 60 min for all X, Y, Z direction |
|---|---|
| Shock Test (Operating) | IEC 60068-2-27, 27, Half Sine Wave: 4G for duration of 22ms; 3 time per direction, 9 times in total |
| Operating Temperature | -20°C to +70°C |
| Storage Temperature | -40°C to +85°C |
| Power De-rating | > 40°C de-rate power by 1.67% / °C @ 115Vac (90-229Vac) / > 50°C de-rate power by 2.5% / °C @ 230Vac (230-264Vac) / < 100Vac de-rate power by 1% / Vac |
| Operating Humidity | 5 to 95% RH (Non-Condensing) |
| Shock Test (Non-Operating) | IEC 60068-2-27, 27, Half Sine Wave: 50G for duration of 22ms; 3 times per direction, 9 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, Random: 5Hz to 500Hz; 2.09Grms; 20 min per axis for all X, Y, Z directions |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Pollution Degree | 2 |
| Overvoltage | 28.8V-35.2V, SELV Output, Latch Mode |
|---|---|
| Overload / Overcurrent | 109-130% of rated load current, Continuous current |
| Over Temperature | Latch Mode |
| Short Circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Degree of Protection | IP20 |
| Protection Against Shock | Class I with Primary Earth connection |
| MTBF | Telcordia SR-332: > 700,000 hrs / I/P: 100Vac, O/P: 100% load, Ta: 25°C |
|---|---|
| Expected Cap Life Time | 10 years (115Vac & 230Vac, 50% load @ 40°C) |
| Electrical Safety | TUV Bauart: : EN 60950-1, EN 62368-1 / UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E131881), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E131881) / CB scheme: IEC 60950-1, IEC 62368-1 |
|---|---|
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| Galvanic Isolation | Input to Output: 3.0KVac / Input to Ground: 2.0KVac / Output to Ground: 0.5KVac |
| Industrial Control Equipment | UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E338991) |
| Safety Entry Low Voltage | SELV |
| UKCA | In conformance with Electrical Equipment (Safety) Regulations 2016 and Electromagnetic Compatibility Regulations 2016 |
| Emission | (CE & RE) / Generic Standards: EN/BS EN 61000-6-3, EN/BS EN 61000-6-4 / CISPR 32, EN/BS EN 55032, EN/BS EN 55011, FCC Title 47: Class B; GB9254.1 |
|---|---|
| Immunity | Generic Standards: EN/BS EN 61000-6-1, EN/BS EN 61000-6-2, EN/BS EN 55024 |
| Harmonic Current Emissions | IEC/EN/BS EN 61000-3-2, Class A; GB17625.1 |
| Voltage Fluctuation and Flicker | IEC/EN/BS EN 61000-3-3 |
| Component Power Supply for General Use | EN/BS EN 61204-3 |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.