Delta DRF-48V480W1PBA 48V 10A 480W DIN Rail Power Supply, DIN Pro Series
- Brand
- Delta
- Model number
- DRF-48V480W1PBA
- Category
- DIN-Rail Power Supplies
DIN Pro DIN rail power supply with 48V 10A output (480W) from 85-277 Vac or 100-400 Vdc. Aluminium and steel case and convection cooling, operating -40 to +80 °C. With power boost, a DC OK signal and remote on/off.
Price and availability on request
Key features
- Wide AC input voltage range 85-277 V (305 V / 60 s)
- Power Boost up to 150% for 5 seconds
- Full load operating temperature up to 60°C
- Wide operating temperature range from -40 to 80°C
- Built-in DC OK relay and LED indicator
- Built-in remote ON / OFF control
- Meet IEC 61000-4-6 CS 20V rms
- Slim profile design
- Conformal coating on PCBAs to protect against common dust and pollutants
- IEC/EN/UL 62368, IEC/UL 61010, and IEC 61558 certified
- Compliant with SEMI F47 standard
Specifications
| Series | DIN Pro Series |
|---|---|
| Mounting | DIN rail |
| Output Current | 10A |
|---|---|
| Output Voltage | 48V |
| Output Voltage Adjustment Range | 48-56 Vdc |
| Output Power | 480W |
| Line Regulation | ± 0.5% @ 230 Vac |
| Load Regulation | ± 0.5% @ 230 Vac |
| PARD | < 150 mVpp @ 0°C to +70°C / < 450 mVpp @ -30°C to 0°C |
| Start-up Time | 800 ms typ. @ 230 Vac |
| Hold-up Time | 25 ms typ. @ 230 Vac (100% load) |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 10% @ 115 Vac & 230 Vac input, 10-100% load (Slew Rate: 2.5 A/μS, 50% duty cycle @ 5 Hz & 10 kHz) |
| Start-up with Capacitive Loads | 5,000 µF Max |
| Rise Time | 30 ms typ. @ 115 Vac & 230 Vac |
| Power Boost Duration | 150% Power Boost for 5 seconds / 200% for 50ms / 500% for 5ms |
| Nominal Input Voltage | 100-240 Vac |
|---|---|
| Input Voltage Range | 85-277 Vac (305 Vac available for 60 seconds) |
| Nominal Input Frequency | 50-60 Hz |
| Input Frequency Range | 47-63Hz |
| DC Input Voltage Range | 100-400 Vdc |
| Input Current | 4.7 A typ. @ 115 Vac, 2.4 A typ. @ 230 Vac |
| Efficiency at 100% load | 95.5% typ. @ 230 Vac |
| Inrush Current | 40 A typ. @ 230 Vac |
| Power Factor at 100% load | > 0.98 @ 115 Vac & > 0.95 @ 230 Vac |
| Leakage Current | < 1.1 mA @ 230 Vac |
| No Load Power Consumption | 2.6 W typ @ 230 Vac |
| Case Chassis / Cover | Galvanized steel with organic coating / Aluminum alloy with organic coating |
|---|---|
| Indicator | Green LED DC OK |
| Cooling System | Convection |
| Input Terminal | 3 Pins (Rated 600 V / 30 A) |
| Output Terminal | 4 Pins (Rated 600 V / 30 A) |
| Signal Terminal | 4 Pins (Rated 300 V / 7 A) |
| Noise Sound Pressure Level (SPL) | Standard TS35 DIN Rail in accordance with EN 60715 |
| Wire | Input: AWG 18-10 / Output: AWG 12-10 / DC OK & Remote: AWG 22-18 |
| Unit Weight | 0.88 kg (1.94 lb) |
| Dimensions | 124.2 x 56 x 117.1 mm / 4.89” x 2.20” x 4.61” |
| Vibration (Operating) | IEC 60068-2-6, Sine Wave: 10 Hz to 500 Hz (2G peak); 10 min per cycle, 60 min for X, Y, Z direction |
|---|---|
| Operating Temperature | -40°C to +80°C |
| Storage Temperature | -40°C to +85°C |
| Power De-rating | Temperature: / > 60°C de-rate power by 2.5 % / °C, > 80°C de-rate power by 3.5% / °C / / Input Voltage: / < 100 Vac de-rate power by 1% / Vac / < 200 Vdc de-rate power by 0.3% / Vdc |
| Operating Humidity | 5 to 90% RH (Non-Condensing) |
| Shock Test (Non-Operating) | IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction, 9 times in total |
| Vibration (Non-Operating) | IEC 60068-2-64, Random: 5 Hz to 500 Hz (2.09 G); 20 min per axis for all X, Y, Z direction |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Pollution Degree | 2 |
| Over Voltage Category | II (Compliance to EN 61558-1 OVC III with 2000 meters altitude) |
| Overvoltage | <69 V, SELV Output, Hiccup Mode, Auto-recovery |
|---|---|
| Overload / Overcurrent | 125 - 205% of rated load current, Hiccup Mode, Auto-recovery (150% Power Boost for 5 seconds / 200% for 50ms / 500% for 5ms) |
| Over Temperature | Shut down, Auto-recovery |
| Short Circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Protection Against Shock | Class I with Primary Earth connection |
| MTBF | Telcordia SR-332: > 700,000 hrs. / I/P: 115 Vac & 230 Vac, O/P: 100% load, Ta: 25°C |
|---|---|
| Expected Cap Life Time | 10 years (115 Vac & 230 Vac, 50% load @ 50°C) |
| Safety Certificate | CB scheme: IEC/EN/BS EN 62368-1, AS/NZS 62368-1 RCM, IEC/EN 61010-1/2-201, IEC 61558-1/2-16, AS/NZS 61558-1/2-16 RCM / TUV Bauart: EN 62368-1 / UL/cUL: UL 62368-1, CSA C22.2; UL 61010-1/-2-201, CAN/CSA-C22.2 No. 61010-1-12 / CCC: GB4943.1 / BIS: IS 13252-1 (Part 1) / BSMI: CNS 15598-1 / EAC: TP TC 004/2011 / KC: KC 62368-1 (upon request) |
|---|---|
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| Galvanic Isolation | Input to Output: 4.0 kVac / Input to Ground: 2.5 kVac / Output to Ground: 1.5 kVac / Output to DC OK: 500 Vac |
| Safety Entry Low Voltage | SELV (IEC/EN 62368-1 /61010-2-201 /61558-2-16) |
| UKCA | In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091 |
| Emission | (CE & RE) / Generic Standards: CISPR 32, EN/BS EN 55032, AS/NZS CISPR 32, Class B; KS C 9832; CNS 15936; EN/BS EN 61204-3; Compliance to FCC Title 47 |
|---|---|
| Immunity | Generic Standards: EN/BS EN 55035; KS C 9835; EN/BS EN 61204-3 |
| Harmonic Current Emissions | IEC/EN/BS EN 61000-3-2, Class A |
| Voltage Fluctuation and Flicker | IEC/EN/BS EN 61000-3-3, dmax ≤ 4% |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.