Delta DRC-12V100W1AZ 12V 6A 72W DIN Rail Power Supply, CHROME Series

Brand
Delta
Model number
DRC-12V100W1AZ

CHROME DIN rail power supply with 12V 6A output (72W) from 90-264Vac or 125-375Vdc. Plastic case and convection cooling, operating -25 to +71 °C. With class II double insulation.

Price and availability on request

Request a quote

Sent with the product details: Delta DRC-12V100W1AZ 12V 6A 72W DIN Rail Power Supply, CHROME Series.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Class II, Double Isolation (No Earth connection is required)
  • Universal AC input voltage range and full power up to 55°C
  • Power will not de-rate for the entire input voltage range
  • Efficiency > 86.0% @ 115 Vac & 230 Vac
  • Can be installed in compact cabinets
  • Low earth leakage current < 0.25 mA @ 264 Vac
  • Conforms to harmonic current IEC/EN 61000-3-2, Class A
  • Safety approval according to IEC/EN/UL 60950-1, IEC/EN/UL 62368-1 and UL 508

Specifications

Product
SeriesCHROME Series
MountingDIN rail
Output
Output Current6A
Output Voltage12V
Output Voltage Adjustment Range12-14Vdc
Output Power72W
Line Regulation< 0.5% (@ 90-264Vac, 100% load)
Load Regulation< 1.0% (@ 90-264Vac input, 0-100% load)
PARD< 100mVpp
Start-up Time< 2,000ms @ nominal input (100% load)
Hold-up Time> 20ms @ 115Vac, / > 100ms @ 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)± 5% @ 90-264Vac input, 10-100% load / (Slew Rate: 0.1A/μs, 50% duty cycle @ 5Hz to 100Hz)
Start-up with Capacitive Loads3,000μF Max
Rise Time< 70ms @ nominal input (100% load)
Input
Nominal Input Voltage100-240Vac
Input Voltage Range90-264Vac
Nominal Input Frequency50-60Hz
Input Frequency Range47-63Hz
DC Input Voltage Range125-375Vdc
Input Current< 1.50A @ 115Vac, / < 1.00A @ 230Vac
Efficiency at 100% load> 86.0% @ 115Vac & 230Vac
Inrush Current< 30A @ 115Vac, / < 65A @ 230Vac
Leakage Current< 0.25mA @ 264Vac
Power Dissipation0% load: < 0.4W @ 115Vac & 230Vac / 100% load: < 11.7W @ 115Vac & 230Vac
Mechanical
Case Chassis / CoverPlastic
IndicatorGreen LED (DC OK)
Cooling SystemConvection
Input Terminal2 Pins (Rated 300V/25A)
Output Terminal4 Pins (Rated 300V/25A)
Noise Sound Pressure Level (SPL)< 25dBA
Mounting RailStandard TS35 DIN Rail in accordance with EN 60715
WireInput/Output: AWG 18-12
Unit Weight0.36 kg (0.79 lb)
Dimensions91 x 89.9 x 55.6 mm / 3.58” x 3.54” x 2.19”
Environment
Vibration (Operating)IEC 60068-2-6, Sine Wave: 10-500Hz; 2G peak; displacement of 0.35mm; 1 octave per min; 60 min per axis for all X, Y, Z directions
Shock Test (Operating)IEC 60068-2-27, Half Sine Wave: 10G for a duration of 11ms; 1 time in X axis
Operating Temperature-25°C to +71°C
Storage Temperature-40°C to +85°C
Power De-rating> 55°C de-rate power by 2.5% / °C
Operating Humidity5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)IEC 60068-2-27, Half Sine Wave: 50G for a duration of 11ms; 3 times per direction, 9 times in total
Vibration (Non-Operating)IEC 60068-2-6, Random: 5-500Hz; 2.09Grms, 20 min per axis for all X, Y, Z directions
Operating Altitude0 to 2,000 Meters (6,560 ft.)
Pollution Degree2
Over Voltage CategoryII
Protections
Overvoltage< 19.0V, SELV Output, Latch Mode
Overload / Overcurrent120-150% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery)
Over Temperature< 75°C Surrounding Air Temperature @ 100% load, Latch Mode
Short CircuitHiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of ProtectionIP20
Protection Against ShockClass II (No Primary Earth connection is required)
Reliability
MTBF> 500,000 hrs. as per Telcordia SR-332 (I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25°C)
Expected Cap Life Time10 years (115Vac & 230Vac, 50% load @ 40°C)
Safety
Electrical SafetyTUV Bauart: EN 62368-1 / UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E131881), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E131881) / CB scheme: IEC 60950-1, IEC 62368-1, Limited Power Source (LPS) / UKCA: BS EN 62368-1
CEIn conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
Galvanic IsolationInput to Output: 3.0 KVac
Industrial Control EquipmentUL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E338991)
Safety Entry Low VoltageSELV (IEC 60950-1)
UKCAIn conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
EMC
Emission(CE & RE) / Generic Standards: CISPR 32, EN/BS EN 55032, FCC Title 47: Class B
ImmunityGeneric Standards: EN/BS EN 55024
Harmonic Current EmissionsIEC/EN/BS EN 61000-3-2, Class A
Voltage Fluctuation and FlickerIEC/EN/BS EN 61000-3-3

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.