| Number of steps for the program | 64 steps for weekly, 32 steps for yearly |
|---|
| Operation mode | Weekly: ON/OFF, pulse, cycle operation Yearly: ON/OFF, pulse operation |
|---|
| Temperature error | ≤ (±0.01%±0.05 sec), at a ratio by the setting time |
|---|
| Cyclic error | ±15 sec/month (25 ℃, ±4 sec/1 week) |
|---|
| Memory retention | ≥ 5 years (25 ℃) |
|---|
| External input | Open or short circuit by a contact device (switch or relay) |
|---|
| Mounting type | Flush mount |
|---|
| Unit weight (packaged) | ≈ 207 g (≈ 337 g) |
|---|
| Power supply | 100 - 240 VAC 50/60 Hz |
|---|
| Permissible voltage range | 90 to 110 % of rated voltage |
|---|
| Power consumption | ≤ 4.2 VA |
|---|
| Control output | Relay |
|---|
| Contact type | SPDT (1c) |
|---|
| Contact capacity | Resistive load: 250 VAC 15 A |
|---|
| Number of circuits | Independent 2 circuits (1c × 2) |
|---|
| Mechanical life expectancy | ≥ 10,000,000 operations (switching capacity: 30 times/min) |
|---|
| Electrical life expectancy | ≥ 50,000 operations (switching capacity: 20 times/min, resistive load: 250 VAC 15 A) |
|---|
| Insulation resistive | ≥ 100 MΩ (500 VDC megger) |
|---|
| Noise immunity | ± 2 kV square-wave noise by noise simulator (pulse width 1 ㎲) |
|---|
| Dielectric strength | Between the charging part and the case : 3,000 VAC at 50 / 60 Hz for 1 min |
|---|
| Vibration | 0.75 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 2 hours |
|---|
| Vibration (malfunction) | 0.5 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 10 min |
|---|
| Shock | 300 m/s2 (≈ 30 G) in each X, Y, Z direction for 3 times |
|---|
| Shock (malfunction) | 100 m/s2 (≈ 10 G) in each X, Y, Z direction for 3 times |
|---|
| Ambient temperature | -10 to 55 ℃, storage: -25 to 65 ℃ (no freezing or condensation) |
|---|
| Ambient humidity | 35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation) |