Autonics FX4Y-I4 Digital Counter / Timer (Indicator) FX4Y-I4

Model number
FX4Y-I4
Category
Counters

Autonics FX4Y-I4 digital counter / timer (Indicator) (FXY Series): 100 - 240 VAC 50 / 60 Hz supply, IP40 (front part, IEC standard). Order code note: 100-240VAC.

Price and availability on request

Request a quote

Sent with the product details: Autonics FX4Y-I4 Digital Counter / Timer (Indicator) FX4Y-I4.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Counting speeds: 1 cps / 30 cps / 2 kcps / 5 kcps
  • Switch between counter and timer operation using DIP switch
  • Switch between voltage input (PNP) and no-voltage input (PNP) using DIP switch
  • Set decimal point, hr / min / sec display with RESET key
  • Operation modes: count-up, count-down, count-up / down (counter) [Counter]
  • 20 input modes [Timer]
  • Various time setting ranges; 6-digit models: 0.01 sec to 99999.9 hr; 4-digit models: 0.01 sec to 9999 hr
  • Power supply; 100 - 240 VAC 50 / 60 Hz (AC type); 24 VAC 50 / 60 Hz, 24 - 48 VDC (AC / DC universal type)

Specifications

Model
SeriesFXY Series
Order code description100-240VAC
Catalogue model groupFX4Y-I□
Specifications
Display digits4-digit
Character sizeW 8 × H 14 mm
Max. counting speed1 / 30 / 2 k / 5 k cps
Return time≤ 500 ms
Min. signal widthINHIBIT, RESET: ≈ 20 ms
Input logicVoltage input (PNP) - input impedance: ≤ 10.8 kΩ, [H]: 5 - 30 VDC , [L]: 0 - 2 VDC No-voltage input (NPN) - s hort-circui t impedance: ≤ 47 0 Ω, short-circuit residual voltage: ≤ 1 VDC open-circuit impedance: ≥ 100 kΩ
ErrorRepeat / SET / voltage / Temp.: ≤ ± 0.01 % ± 0.05 s
Unit weight (packaged)≈ 120 g (≈ 175 g)
Voltage typeAC voltage
Power supply100 - 240 VAC 50 / 60 Hz
Permissible voltage range90 to 110 % of rated voltage
Power consumption≤ 3.8 VA
External supply power≤ 12 VDC ± 10 % 50 mA
Memory retention≈ 10 years (non-volatile semiconductor memory type)
Insulation resistance≥ 100 MΩ (500 VDC megger)
Dielectric strengthBetween the charging part and the case : 3,000 VAC 50 / 60 Hz for 1 min
Noise immunity± 2 kV square wave noise (pulse width: 1 ㎲) by the noise simulator
Vibration0.75 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 1 hour
Vibration (malfunction)0.5 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 10 minute
Shock300 m/s2 (≈ 30 G) in each X, Y, Z direction for 3 times
Shock (malfunction)100 m/s2 (≈ 10 G) in each X, Y, Z direction for 3 times
Ambient temperature-10 to 55 ℃, storage: -25 to 65 ℃ (no freezing or condensation)
Ambient humidity35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)
Protection ratingIP40 (front part, IEC standard)
Accessories
Sold separatelyTerminal protection cover: M7P-COVER

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.