Autonics ATS8SD-4 W 38 × H 42 mm Star-Delta Analog Timer ATS8SD-4

Model number
ATS8SD-4
Category
Timers

Autonics ATS8SD-4 W 38 × H 42 mm Star-Delta analog timer (ATS8SD-4 Series): Relay output, 100 - 240 VAC 50 / 60 Hz, 24 - 240 VDC supply. Order code note: 100-240VAC.

Price and availability on request

Request a quote

Sent with the product details: Autonics ATS8SD-4 W 38 × H 42 mm Star-Delta Analog Timer ATS8SD-4.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Wide power supply range: 100 - 240 VAC 50 / 60 Hz, 24 - 240 VDC
  • Wide time setting range and switching time; T1 (setting time): selectable 0.5 to 100 sec; T2 (switching time): selectable 0.05, 0.1, 0.2, 0.3, 0.4, 0.5 sec
  • Close and DIN rail mounting with the dedicated socket (PS-M8) width 41 mm
  • Easy installation / maintenance with the dedicated bracket for DIN 48 × 48 mm
  • Application: Starting large capacity motors

Specifications

Model
SeriesATS8SD-4 Series
Order code description100-240VAC
Catalogue model groupATS8SD-4□
Specifications
FunctionStar-Delta Timer
Return time≤ 100 ms
Time operationPower ON Start
Control outputRelay
Contact typeY Contact: Time limit SPST (1a), ∆Contact: Time limit SPST (1a)
Contact capacity250 VAC 3 A, 30 VDCc 3 A resistive load
ErrorRepeat: ≤ ± 0.2% ± 10 ms Voltage: ≤ ± 0.5% Temp.: ≤ ± 2% Y setting time : ≤ ± 5% ± 50 ms Y -∆switching time: ≤ ± 25%
Unit weight≈ 72 g
Power supply100 - 240 VAC 50 / 60 Hz, 24 - 240 VDC
Permissible voltage range90 to 110 % of rated voltage
Power consumptionAC: ≤ 3 VA, DC: ≤ 1.5 W
Insulation resistive≥ 100 MΩ (500 VDC megger)
Dielectric strengthBetween the charging part and the case : 3,000 VAC at 50 / 60 Hz for 1 min
Noise immunity± 2 kV square-wave noise by noise simulator (pulse width 1 ㎲)
Vibration0.75 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 1 hour
Vibration (malfunction)0.5 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 10 min
Shock300 m/s2 (≈ 30 G) in each X, Y, Z direction for 3 times
Shock (malfunction)100 m/s2 (≈ 10 G) In each X, Y, Z direction for 3 times
Relay life cycleMechanical: ≥ 10,000,000 operations Electrical: ≥ 100,000 operations (250 VAC 3 A resistive load)
Ambient temperature-10 to 55 ℃, storage: -25 to 65 ℃ (no freezing or condensation)
Ambient humidity35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
Accessories
Sold separately8-pin controller socket: PG-08, PS-08(N), PS-M8

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.