Autonics ATS8P-2M W 38 × H 42 mm Power OFF Delay Analog Timer ATS8P-2M

Model number
ATS8P-2M
Category
Timers

Autonics ATS8P-2M W 38 × H 42 mm power OFF delay analog timer (ATS8P Series): Relay output, 24 VAC 50 / 60 Hz, 24 VDC supply. Order code note: 24VAC/DC(NEW).

Price and availability on request

Request a quote

Sent with the product details: Autonics ATS8P-2M W 38 × H 42 mm Power OFF Delay Analog Timer ATS8P-2M.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Control time range (ATS8P- S: 0.1 to 10 sec, ATS8P- M: 0.1 to 10 min)
  • Direct reading for time setting and time range with easy adjustment
  • Power supply: 100 - 120 VAC 50 / 60 Hz, 200 - 240 VAC 50 / 60 Hz, 24 VAC 50 / 60 Hz, 24 VDC universal
  • Close and DIN rail mounting with the dedicated socket (PS-M8) width 41 mm
  • Easy mounting and installation / maintenance with the dedicated bracket for DIN 48 × 48 mm
  • Application: Protection circuit when momentary power failure and start it again

Specifications

Model
SeriesATS8P Series
Order code description24VAC/DC(NEW)
Catalogue model groupATS8P-2□
Specifications
FunctionPower OFF Delay
Return time≤ 100 ms
Control outputRelay
Contact typeTime limit DPDT (2c)
Contact capacity250 VAC 3 A, 30 VDC 3 A resistive load
ErrorRepeat: ≤ ± 0.2% ± 10 ms SET: ≤ ± 5% ± 50 ms Voltage: ≤ ± 0.5% Temp.: ≤ ± 2%
Time operationPower OFF Start
Unit weightSEC unit model: ≈ 80 g, MIN unit model: ≈ 85 g
Power supply24 VAC 50 / 60 Hz, 24 VDC
Permissible voltage range90 to 110 % of rated voltage
Power consumptionAC: ≤ 0.2 VA DC: ≤ 0.2 W
Insulation resistive100 MΩ (500 VDC megger)
Dielectric strengthBetween the charging part and the case : 3,000 VAC at 50 / 60 Hz for 1 min
Noise immunity± 2 kV square-wave noise by noise simulator (pulse width 1 ㎲)
Vibration0.75 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 1 hour
Vibration (malfunction)0.5 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 10 min
Shock300 m/s2 (≈ 30 G) in each X, Y, Z direction for 3 times
Shock (malfunction)100 m/s2 (≈ 10 G) In each X, Y, Z direction for 3 times
Relay life cycleMechanical: ≥ 10,000,000 operations Electrical: ≥ 100,000 operations (250 VAC 3 A resistive load)
Ambient temperature-10 to 55 ℃, storage: -25 to 65 ℃ (no freezing or condensation)
Ambient humidity35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
Accessories
Sold separately8-pin controller socket: PG-08, PS-08(N), PS-M8

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.