| Function | Multi Function Timer |
|---|
| Return time | ≤ 100 ms |
|---|
| Time operation | Signal ON Start |
|---|
| Input | START, INHIBIT, RESET |
|---|
| Min. signal width | ≈ 50ms |
|---|
| No-voltage input | Short-circuit impedance: ≤ 1 kΩ Short-circuit residual voltage: ≤ 0.5 VDC Open-circuit impedance: ≥ 100 kΩ |
|---|
| Control output | Relay |
|---|
| Contact type | Time limit DPDT (2c) |
|---|
| Contact capacity | 250 VAC 3 A, 24 VDC 3 A resistive load |
|---|
| Error | Repeat: ≤ ± 0.2% ± 10 ms SET: ≤ ± 5% ± 50 ms Voltage: ≤ ± 0.5% Temp.: ≤ ± 2% |
|---|
| Unit weight (packaged) | ≈ 70 g (≈ 95 g) |
|---|
| Power supply | 24 VAC 50 / 60 Hz, 24 VDC |
|---|
| Permissible voltage range | 90 to 110 % of rated voltage |
|---|
| Power consumption | It depends on the plug type and output. |
|---|
| ATS8- | AC: ≤ 4.5 VA DC: ≤ 2 W |
|---|
| ATS11- D | AC: ≤ 4 VA DC: ≤ 1.5 W |
|---|
| ATS11- E | AC: ≤ 4.5 VA DC: ≤ 2 W |
|---|
| Insulation resistive | ≥ 100 MΩ (500 VDC megger) |
|---|
| Dielectric strength | Between the charging part and the case : 3,000 VAC at 50 / 60 Hz for 1 min |
|---|
| Noise immunity | It depends on the power supply. |
|---|
| ATS -1 | ± 500 V square-wave noise by noise simulator (pulse width 1 ㎲) |
|---|
| ATS -4 | ± 2kV square-wave noise by noise simulator (pulse width 1 ㎲) |
|---|
| Vibration | 0.75 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 1 hour |
|---|
| Vibration (malfunction) | 0.5 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 10 min |
|---|
| Shock | 300 m/s2 (≈ 30 G) in each X, Y, Z direction for 3 times |
|---|
| Shock (malfunction) | 100 m/s2 (≈ 10 G) In each X, Y, Z direction for 3 times |
|---|
| Relay life cycle | Mechanical: ≥ 10,000,000 operations Electrical:≥ 100,000 operations (250 VAC 3 A resistive load) |
|---|
| Ambient temperature | -10 to 55 ℃, storage: -25 to 65 ℃ (no freezing or condensation) |
|---|
| Ambient humidity | 35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation) |