Yokogawa CL155 Clamp-on Meter Tester CL155 (AC, True RMS, 2000A)
- Brand
- Yokogawa
- Model number
- CL155
- Category
- AC Clamp Meters
Clamp-on Tester CL155 (AC, True RMS, 2000A), AC current measurement with current ranges up to 2000A, AC/DC voltage, and resistance measurements.
Price and availability on request
We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.
Several models? Add each to your enquiry list and send them as one enquiry.
Key features
- Display (LCD, Digital Counts) - 3999
- AC Current Accuracy (400A Reference) - 1.0+3(50/60Hz) 2.0+3(40~1kHz)
- AC Current Accuracy (2000A Reference, 0~1500A) - 2.0+3(50/60Hz) 3.0+3(40~1kHz)
- AC Voltage Accuracy (40/ 400V/ 750V Reference) - 1.0+2(50/60Hz) 1.5+3(40~1kHz)
- DC Voltage Accuracy (40/ 400V/ 1000V Reference) - 1.0+2
Specifications
| Display (LCD, Digital Counts) | 3999 |
|---|---|
| AC Current Accuracy (400A Reference) | 1.0+3(50/60Hz) 2.0+3(40~1kHz) |
| AC Current Accuracy (2000A Reference, 0~1500A) | 2.0+3(50/60Hz) 3.0+3(40~1kHz) |
| AC Voltage Accuracy (40/ 400V/ 750V Reference) | 1.0+2(50/60Hz) 1.5+3(40~1kHz) |
| DC Voltage Accuracy (40/ 400V/ 1000V Reference) | 1.0+2 |
| Resistance Accuracy (400/ 4k/ 40k/ 400kΩ reference) | 1.5+2, Beeps at below 50± 35Ω (continuity check) |
| DC Output Accuracy (400A, 0~400mV Reference) | ۫.5% rdg ± 0.5mV (50/60Hz) ۬.5% rdg ± 0.5mV (40~1kHz) |
| Method of detection | True RMS |
| Response Time | Approx. 2 seconds |
| Range Switching | Manual-range (on AC current range) / Auto-range (on AC voltage range, resistance range) |
| Data hold | On all range |
| Operating temperature and humidity | 0-40°C, 85% RH or less (no condensation) |
| Influence of external magnetic field | 1A or less at 400A/m |
| Influence of conductor position | ± (2.0% rdg + 3dgt) or less |
| Safety Standard | Conforms EN 61010-1, EN61010-2-031, EN61010-2-032 |
| Circuit voltage | 1000Vrms or less |
| Withstanding voltage | 5.55kV AC for one minute |
| Power Supply | R6P(SUM-3)x2 or LR6x2 |
| Battery Life1 | 150 hours |
| Consumed current | Approx. 5mA |
| Sleep Function | Automatically powered down in about 10 minutes after the last switch operation |
| Diameter of measurable conductor | 54mm at maximum |
| Dimensions | Approx. 105(W)x247(H)x49(D)mm |
| Weight (Approx.) | 470g |
| Accessories | Clamp Adapter (Model 99025), Output Cable for Terminal Screw (Model 91019), Carrying Case (Model 93034), Output Plug (Model 98012), Test Lead (Model 98011) User's manual (IM CL120), batteries |
| Order Notes | Each item selected MUST be ordered as a separate line item. |
| Product Notes | All Clamp-on Meters include Test Leads (where applicable) and a carrying case. |
| AC Current Range | 400/2000A |
| AC Current Resolution | 0.1A |
| AC Current Frequency characteristics | 40~1kHz |
| AC Current Method of detection | True RMS |
| AC Voltage Measurement | O |
| DC Voltage Measurement | O |
| Continuity Check Measurement | O |
| Frequency Measurement | - |
| Temperature Measurement | - |
| Recorder output Function | O |
| Waveform monitor output Function | - |
| Data hold Function | O |
| Auto hold Function | - |
| Peak Hold Function | O |
| Maximum value memory Function | - |
| Mean value display Function | - |
| Filter Function | - |
| Range Hold Function | O (current range) |
| Auto ZERO Adjust Function | - |
| Auto power-off Function | O Sleep function (power-down) |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details
About the CL155
Yokogawa Clamp-on Meter Tester CL155 (AC, True RMS, 2000A). Clamp-on Tester CL155 (AC, True RMS, 2000A), AC current measurement with current ranges up to 2000A, AC/DC voltage, and resistance measurements.