WIKA TSM-550 Capillary Temperature Switch, 25 to 300 C, IP67

Brand
WIKA
Model number
TSM-550

Vapour-pressure temperature switch with bulb and 3, 5 or 8 m armoured capillary for pumps, lubrication, hydraulics, HVAC and turbines. Ranges 25 ... 90 to 200 ... 300 C, SPDT, IP67. Formerly RT-101 series.

Price and availability on request

We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.

Several models? Add each to your enquiry list and send them as one enquiry.

Request a quote

Sent with the product details: WIKA TSM-550 Capillary Temperature Switch, 25 to 300 C, IP67.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Five setting ranges from 25 C to 300 C
  • Adjustable switch point and on-off differential
  • Copper or stainless steel bulb with armoured capillary, 3, 5 or 8 m
  • Optional brass or stainless steel thermowell
  • Snap-action switch, repeatability ±1 % of full scale
  • Weatherproof IP67 enclosure
  • Replaces the earlier RT-101, RT-107, RT-120, RT-123 and RT-124

Specifications

Versions
TSM-550-T1 (old RT-101)25 ... 90 C
TSM-550-T2 (old RT-107)70 ... 150 C
TSM-550-T3 (old RT-120)120 ... 215 C
TSM-550-T4 (old RT-123)150 ... 250 C
TSM-550-T5 (old RT-124)200 ... 300 C, stainless steel bulb only
Capillary length3, 5 or 8 m, shown in brackets in the order code, e.g. TSM-550-T1 (5); 3 m and 8 m for T3 and T4 are non-standard
Switching
Repeatability±1 % of full scale
Electrical
Switch contact1 SPDT contact system, 1 SPDT microswitch or 1 DPDT microswitch
Electrical ratingAC 230 V: 10 A resistive (AC-1), 4 A inductive (AC-15)
Connections
Electrical connection½ NPT female conduit entry
Ingress protectionIP67
Bulb9.5 mm dia. copper (standard) or 304 stainless steel; T5 11 mm stainless steel
Operating conditions
Ambient temperature-40 ... +70 C
Materials
CapillaryTin-plated copper with stainless steel armour
EnclosureABS cover and DMC housing (standard) or die-cast aluminium
General
Data sheetWIKA TSM-550

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details

Model numbers in this series (10)

Send us the complete code you need and we will quote it.

  • TSM-550-T1
  • TSM-550-T2
  • TSM-550-T3
  • TSM-550-T4
  • TSM-550-T5
  • RT-101
  • RT-107
  • RT-120
  • RT-123
  • RT-124