Veritek VIPS-AT-LD Current Protection Relay with LCD
- Brand
- Veritek
- Model number
- VIPS-AT-LD
- Category
- Protection & Monitoring Relays
Current protection relay with LCD and bar graph: under/over current, phase loss and reversal, frequency, locked rotor; two relays.
Price and availability on request
Key features
- 1Ø-2 Wire, 3Ø-4 Wire Input
- Autoranging Current display
- User settable trip level and time delay
- Under Current
- Over Current
- Current frequency
- Under frequency
- Locked Rotor
- Din rail mounting
- Password protection
- Two Relays Output
- Auto / Manual Reset user Programmable
- Power ON Delay user Programmable
- Bargraph Display for current in percentage of full scale
- True RMS Measurement
- Two Alarm Relay with NC or NO operation selectable
Specifications
| Display | LCD (Displays actual current in amps, Frequency and current asymmetry) |
|---|---|
| Bargraph | % of full scale |
| Reset | Auto / Manual Programmable |
| Time Delay | Power ON, Trip Time, Recovery Time |
| CT Primary | 1A - 5.00 KA |
| CT Secondary | 1A/5A |
| Measuring Range | 0.01-6.00 Amps, 45-65 Hz |
| Set Points | Under Current: 2-100% of CT primary; Over Current: 10-120% of CT primary; Current Asymmetry: 5-99.9%; Over Frequency: 45-65 Hz; Under Frequency: 45-63 Hz; Locked rotor: 2-10 Times of overload; Phase loss: 150% of Overload |
| Power ON Delay | 0 - 99.9 sec |
| Trip Time Delay | 0 - 99.9 sec |
| Recovery Time Delay | 0 - 99.9 sec (auto reset) |
| Response Time | ≤ 200 ms |
| Hysteresis | Current: 0.1Amps-3.50Amps; Frequency: 0.2-2.0Hz; Asymmetry: 2.0-20.0% |
| Current Resolution | Auto ranging (0.01A to 0.01kA) |
| Current Accuracy | ± 1% of set point, ± 2 Counts |
| Time Setting Accuracy | ± 5% of setting |
| Status of Relay | Programmable |
|---|---|
| Relay Rating | NO (5A and 240V AC) |
| Type of O/P (Relay 1) | 1 C/O (SPDT) |
| Type of O/P (Relay 2) | 1 C/O (SPDT) |
| Alarm Indication | R1 & R2 LED |
| Connection | 1Ø-2 wire, 3Ø-4 wire |
|---|---|
| Weight | 200 g |
| Dimensions | 93 X 35 X 68 mm (LxBxH) |
| Mounting | Din rail Mount |
| Enclosure | ABS Thermoplastic |
| Protections | Under Current, Over Current, Phase loss, Phase reversal, Under frequency, Over frequency, Locked rotor |
| Supply Voltage | 90-270V AC/DC |
|---|---|
| Supply Frequency | 50/60 Hz |
| Power Consumption | 3 VA max |
| Humidity | Up to 95% RH |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.