Veritek VIPS 98LD Earth Leakage Relay with Display, DIN Rail

Brand
Veritek
Model number
VIPS 98LD

DIN-rail earth leakage relay with LCD display and bar graph, 10 mA – 30 A, pre-alarm, two relays, password, auto/manual reset.

Price and availability on request

Request a quote

Sent with the product details: Veritek VIPS 98LD Earth Leakage Relay with Display, DIN Rail.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Leakage Current display
  • User settable trip level and timer delay
  • DIN Rail mount
  • Password protection
  • Bar graph display for leakage current in percentage of set point
  • Two Relays Output
  • CBCT open circuit detection
  • Auto / Manual Reset

Specifications

Specifications
DisplayLCD (Displays actual leakage current in amps)
Bar graphPercentage of leakage Current Setting
ResetAuto / Manual Programmable
Time DelayPower ON, Trip Time, Recovery Time
CBCT Sizes35mm, 50mm, 70mm, 120mm, 160mm, 210mm and 310mm
Measuring Range10mA - 30A, 50 - 60Hz
Set Points1A - (0-999 mA); 10A - (1-9.99 A); 30A - (10-30 A)
Power ON Delay0 - 99.9 sec
Trip Time Delay0 - 99.9 sec
Recovery Time Delay0 - 99.9 sec (auto reset)
Response Time≤ 25 msec
Hysteresis3 - 25% of set value
Current ResolutionAuto ranging
Current Accuracy± 5% of setting (± 2 count)
Time Setting Accuracy± 5% of setting
Outputs
Status of RelayProgrammable - Normally De-energized / Positive Safety
Relay RatingNO (5A and 240V AC), NC (5A and 240V AC)
Type of O/P (Relay 1)1 C/O (SPDT)
Type of O/P (Relay 2)1 C/O (SPDT)
Alarm IndicationPre-warning alarm, Trip, CBCT error
Pre-Alarm50 - 90 % of Leakage Current Setting
Supply
Supply Voltage90-270VAC/DC
Supply Frequency50/60 Hz
Power Consumption3VA max
Environmental
Operating Temperature-10°C to 55°C
Storage Temperature-10°C to 70°C
HumidityUp to 95% RH
Mechanical
Weight228 g
Dimensions93 X 35 X 68 mm (LxBxH)
MountingDin Rail Mount
EnclosureABS Thermoplastic

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.