SEW 1812 EL-A Digital RCD / GFCI / ELCB Tester

Brand
SEW
Model number
1812 EL-A

Microprocessor RCD / ELCB tester with a 2-line LCD: 18 trip-current settings from 3 mA to 500 mA, 0° or 180° start, digital trip-time readout to 1 ms, L-E voltmeter and wiring polarity check.

Price and availability on request

Request a quote

Sent with the product details: SEW 1812 EL-A Digital RCD / GFCI / ELCB Tester.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Microprocessor-controlled
  • 2 lines x 16 characters LCD
  • Very low consumption
  • Menu-driven
  • Accurate digital readout of disconnection time
  • Automatic data hold function
  • Zero crossing circuitry permits testing at 0° or 180°
  • Disconnection phase polarity shown on LCD display
  • Auto-off and off override
  • Polarity trip indicator (positive or negative phase)
  • Wiring polarity indicator
  • Measures voltage and frequency between Line and Earth before testing

Specifications

Test
Current settings3mA, 5mA, 7mA, 10mA, 15mA, 20mA, 30mA, 35mA, 50mA, 100mA, 125mA, 150mA, 175mA, 250mA, 275mA, 300mA, 375mA, 500mA
Current selectionRotary switch selector
Current accuracy±5% ±1mA
Phase start selection 0° and 180°Yes, referenced to Earth
Timer resolution / accuracy1ms (max. time 2.999s) / ±2% ±2ms
Indication
Wiring correctnessYes (LEDs)
Trip indicatorYes (LCD)
Phase polarity trip indicatorYes (LCD), referenced to Earth
Voltmeter
Range (L-E)20Vac ~ 280Vac
Resolution / accuracy1Vac / ±2% ±1Vac
General
Versions1812 EL-A A 240Vac; B 230Vac; C 220Vac; D 110Vac
Over-temperature protectionYes (3 sensors)
Operating temperature-5°C to 45°C
Storage temperature-10°C to 55°C
Dimensions170 (L) x 165 (W) x 92 (D) mm
WeightApprox. 1020g (battery included)
Power source1.5V (AA) x 8
Safety standardEN 61010-1 CAT III 240V, EN 61326-1
Supplied with
Standard accessoriesInstruction manual; test leads; shoulder belt; batteries

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.