SBEM 133 TWT Two-Wire Tank Level Transmitter with Limit Switches

Brand
SBEM
Model number
133 TWT

Two-wire tank level transmitter with 4-20 mA output and 2 or 4 adjustable limit switches in one flameproof, IP65 housing, ranges 8 to 24 m, intrinsically safe for hazardous areas.

Price and availability on request

We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.

Several models? Add each to your enquiry list and send them as one enquiry.

Request a quote

Sent with the product details: SBEM 133 TWT Two-Wire Tank Level Transmitter with Limit Switches.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Combined 4-20 mA output and limit switches in one enclosure
  • Level ranges of 8000, 12000, 16000 or 24000 mm
  • Limit switches with 2 or 4 contacts and adjustable setpoints
  • Repeatable alarm switching
  • Settings adjustable without changing the tank level
  • Intrinsically safe certification (requires barriers or isolators)

Specifications

Specifications
TypeFlameproof as per IS:2148-1981, suitable for Gr IIA and IIB areas
CertificateCMRI/TC/H554 dated 19/12/96 issued by CMRI, Dhanbad
WeatherproofIP65 as per IS:2147-1962
Cable entries4 nos., standard 1/2" NPT(F)
Range8000 / 12000 / 16000 / 24000 mm (factory set)
Output4 to 20 mADC
Input sensor3-wire precision multi-turn wire-wound potentiometer
Source voltageMax. 36 VDC; min. 12 + (0.02 x loop resistance in Ω) VDC
Minimum span25% of range
Accuracy±0.75% for ranges below 6000 mm; ±0.50% for ranges above 6000 mm
TerminalsConductor up to 2.5 mm²
Number of switches2 or 4
Range of adjustment0 to 50% for LO and LO-LO; 50 to 100% for HI and HI-HI
Repeatability±20 mm
Hysteresis40 / 55 / 70 / 100 mm for 8000 / 12000 / 16000 / 24000 mm ranges
Contact ratingMicroswitch, 5 A at 230 VAC or 2 A at 24 VDC (resistive)
Contact configuration1 c/o per limit switch
Setpoint spacingMinimum distance between two setpoints = hysteresis + 50 mm

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details

About the 133 TWT

Two-wire tank level transmitter with 4-20 mA output and 2 or 4 adjustable limit switches in one flameproof, IP65 housing, ranges 8 to 24 m, intrinsically safe for hazardous areas. Typical applications: Tank inventory management; Tank level monitoring and control; High and low level alarms; Hazardous-area installations in oil, gas and chemical sectors.

Frequently asked questions

What is the SBEM 133 TWT?

Two-wire tank level transmitter with 4-20 mA output and 2 or 4 adjustable limit switches in one flameproof, IP65 housing, ranges 8 to 24 m, intrinsically safe for hazardous areas.

What is the accuracy of the 133 TWT?

±0.75% for ranges below 6000 mm; ±0.50% for ranges above 6000 mm.

What is the measuring range of the 133 TWT?

Range: 8000 / 12000 / 16000 / 24000 mm (factory set); Range of adjustment: 0 to 50% for LO and LO-LO; 50 to 100% for HI and HI-HI.

What output does the 133 TWT give?

4 to 20 mADC.