Rishabh Relay VR-1 Single Phase Voltage Protection Relay
- Brand
- Rishabh
- Model number
- Relay VR-1
- Category
- Protection & Monitoring Relays
Self-powered 17.5 mm single-phase voltage relay with on-site nominal voltage, trip points (OV 105 - 125%, UV 75 - 95%) and 0 - 10 s delay; protects against over and under voltage.
Price and availability on request
Key features
- Compact 17.5 mm width
- True RMS measurement
- Protection against over and under voltage
- Adjustable nominal voltage, trip point and trip time delay
- Over and under voltage faults can be disabled on site
- Self powered
- 1 CO or 1 CO + 1 CO relay configuration
- LED indication for faults
- Applications: motor protection, server rooms, control systems
Specifications
| Nominal voltage (Vn) | 1 phase L: 58 - 63 - 110 - 120 - 127 - 138 V L-N; H: 220 - 230 - 240 - 254 V L-N, programmable on site |
|---|---|
| Max. continuous input voltage | 127% of nominal value |
| Nominal frequency | 50 / 60 Hz |
| Burden | < 2 VA approx. per phase |
| Voltage range | 70 - 125% of nominal value |
| Over voltage trip point | 105 - 125% (variable) |
|---|---|
| Under voltage trip point | 75 - 95% (variable) |
| Hysteresis | 3% (fixed) of trip point |
| Trip delay | 0 - 10 s variable for under voltage, over voltage |
| Reset delay | 1 s (fixed) |
| Power on delay | Approx. 3 s (fixed) |
| Tripping | ±3% of nominal value; ±0.8 s for trip delay |
|---|---|
| Response time | Less than 200 ms |
| Types | 1 CO or 1 CO + 1 CO (normally energized; de-energized on request) |
|---|---|
| Rating | 5 A / 250 V AC / 30 V DC (resistive load) |
| Mechanical endurance | 1 x 10^7 operations |
| Electrical endurance | 1 x 10^5 operations |
| Operating temperature | -10 to +55 °C |
|---|---|
| Storage temperature | -25 to +70 °C |
| Relative humidity | 0 - 90% non condensing |
| Shock | 15g in 3 planes |
| Vibration | 10 - 55 Hz, 0.15 mm amplitude |
| Enclosure | IP20 (front face only) |
| Dimensions | 18 x 98.6 x 66.5 mm (17.5 mm wide module) |
| Weight | 80 g approx. |
| Safety | IEC 61010-1-2010 |
|---|---|
| Installation category | CAT III, pollution degree 2 |
| High voltage test | 2.2 kV AC, 50 Hz for 1 minute between all electrical circuits |
| Order code | VR-1-[L / H]-[1 / 2 relays], e.g. VR-1-H-1 |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.