Rishabh Relay V/Hz Line Monitoring Relay (Voltage and Frequency)
- Brand
- Rishabh
- Model number
- Relay V/Hz
- Category
- Protection & Monitoring Relays
Digital line monitoring relay cum class 0.5 DPM: over / under voltage, phase failure, unbalance, incorrect sequence and over / under frequency protection, PT ratio programmable, 2 relays.
Price and availability on request
Key features
- Over / under voltage, phase failure (single phasing), phase unbalance and incorrect phase sequence protection
- Over and under frequency protection
- 4-digit ultra bright 7 segment LED display; trip relay cum DPM with class 0.5
- True RMS measurement up to 15th harmonic
- User selectable 1P2W / 3P4W / 3P3W network and phase sequence (123 or 321)
- User selectable PT primary (100 V L-L to 1200 kV L-L) and PT secondary (100 - 600 V L-L)
- Stores the last 15 faults
- AND function: trip on any two fault conditions
- Trip or buzzer mode
- Auto / manual reset
- Dual colour LED per phase plus relay 1 / relay 2 status LEDs
- Configuration via USB-based PRKAB
- Applications: standby generators and gensets (AVR monitoring), mains failure units, UPS change-over, voltage-sensitive motors, computer supplies
Specifications
| Nominal input voltage | 600 V L-L (346.42 V L-N) |
|---|---|
| PT secondary | 100 V L-L to 600 V L-L programmable on site |
| PT primary | 100 V L-L to 1200 kV L-L programmable on site |
| Max. continuous input voltage | 127% of PT secondary |
| Voltage burden | < 0.6 VA approx. |
| Overload withstand | 2 x rated value for 1 s, repeated 10 times at 10 s |
| Measuring range | Voltage 20 - 125% of PT secondary, frequency 40 - 70 Hz |
| Nominal frequency | 50 / 60 Hz programmable on site |
| Voltage / frequency | ±0.5% of nominal value / ±0.2 Hz |
|---|---|
| Delays | ±140 ms or ±5% of set delay, whichever is greater |
| Higher aux | 60 V - 300 V AC/DC (nominal 230 V AC/DC, 50/60 Hz for AC) |
|---|---|
| Lower aux | 20 V - 60 V DC / 20 V - 40 V AC (nominal 48 V DC / 24 V AC) |
| Frequency | 45 to 66 Hz |
| Burden | < 4 VA approx. |
| Phase failure | 20 - 85% |
|---|---|
| Voltage unbalance | 2 - 20% |
| Over / under voltage | 101 - 125% / 70 - 99% |
| Max. / min. frequency | 101 - 110% / 90 - 99% |
| Trip delays | 0 - 30 s (each fault) |
| Fault deactivation | Individual faults can be deactivated (not phase failure) |
| Reset delay | 0.2 - 30 s |
| Power on delay | 0.5 - 30 s |
| Reset option | Auto / manual |
| Relay control mode | De-energize / energize |
| Differential / hysteresis | 1 - 15% |
| Types | 1 CO, 2 CO or 1 CO + 1 CO |
|---|---|
| Rating | 5 A / 250 V AC / 30 V DC (resistive load) |
| Mechanical endurance | 1 x 10^7 operations |
| Electrical endurance | NO 3 x 10^4, NC 1 x 10^4 operations (1 CO / 1 CO + 1 CO); 1 x 10^5 operations (2 CO) |
| EMC | IEC 61326-1:2012, Table 2; immunity IEC 61000-4-3 10 V/m |
|---|---|
| Safety | IEC 61010-1-2010, permanently connected use |
| Installation category | 300 V CAT III / 600 V CAT II, pollution degree 2 |
| High voltage test | 2.2 kV AC, 50 Hz for 1 minute |
| Operating temperature | -10 to +55 °C |
|---|---|
| Storage temperature | -25 to +70 °C |
| Relative humidity | 0 - 90% non condensing |
| Shock | 15g in 3 planes |
| Vibration | 10 - 55 Hz, 0.15 mm amplitude |
| Enclosure | IP20 (front face only) |
| Weight | 300 g approx. |
| Order code | RISH Relay V/Hz - [1: single phase / 3: three phase] - [1000: 1 CO / 1001: 1 CO + 1 CO / 1002: 2 CO] - [HA / LA aux] |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.