Rishabh Relay UVR Under Voltage Protection Relay
- Brand
- Rishabh
- Model number
- Relay UVR
- Category
- Protection & Monitoring Relays
Self-powered 17.5 mm under voltage relay: trips below 75% of nominal (3P4W 415/400/380 V or 1P2W 240/230/220 V), adjustable 5 - 15 min restart delay, auto reset, 1 CO contact.
Price and availability on request
Key features
- Fixed under voltage trip at 75% of nominal value
- Adjustable power-on and restart delay from 5 to 15 minutes
- Auto reset, no manual intervention
- True RMS measurement
- Self-powered: no external power supply needed
- LED indications with multiple states for easy diagnosis
- DIN-rail or wall mounting
- Ultra-slim 17.5 mm width
- Applications: motor protection, server rooms, control systems, air conditioning (HVAC) systems
Specifications
| Nominal voltage (fixed) | 3P4W: 415 / 400 / 380 V L-L; 1P2W: 240 / 230 / 220 V L-N |
|---|---|
| Max. continuous input voltage | 127% of nominal value |
| Nominal frequency | 50 / 60 Hz |
| Burden | < 16 VA |
| Voltage range | 70 - 125% of nominal value |
| Under voltage trip point | 75% (fixed) of nominal value |
|---|---|
| Hysteresis | 2% (fixed) of nominal value |
| Restart / power-on delay | 5 - 15 minutes (variable), accuracy ±0.8 s |
| Tripping | ±3% of nominal value |
|---|---|
| Response time | Less than 200 ms |
| Type | 1 CO |
|---|---|
| Rating | 5 A / 250 V AC / 30 V DC (resistive load) |
| Mechanical endurance | 1 x 10^7 operations |
| Electrical endurance | 1 x 10^5 operations |
| Operating temperature | -10 to +55 °C |
|---|---|
| Storage temperature | -25 to +70 °C |
| Relative humidity | 0 - 90% non condensing |
| Shock | 30 gn (300 m/s^2), duration 18 ms (IEC 60068-2) |
| Vibration | 10 - 55 Hz, 0.15 mm amplitude |
| Enclosure | IP 20 |
| Dimensions | 18 x 98.6 x 66.5 mm (17.5 mm wide module) |
| Weight | 80 g approx. |
| Safety | IEC 61010-1-2010 |
|---|---|
| Installation category | CAT III, pollution degree 2 |
| High voltage test | 2.2 kV AC, 50 Hz for 1 minute between all electrical circuits |
| Order code | UV10-V-[3: 3P4W / 1: 1P2W]-[1: 220 / 2: 230 / 3: 240 V L-N]-[frequency]-1-1 |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.