Rishabh Relay I Current Protection Relay
- Brand
- Rishabh
- Model number
- Relay I
- Category
- Protection & Monitoring Relays
Digital current protection relay cum class 0.5 DPM: over current with IDMT curves, under current, current loss and unbalance protection; CT ratio programmable to 999 kA, 2 relay outputs.
Price and availability on request
Key features
- Over current protection with IDMT curves: standard, very, extremely and long inverse (TMS 0.1 - 1)
- Under current, current loss and current unbalance protection
- ANSI functions 37 (under current), 51 (over current), 46 (current unbalance)
- 4-digit ultra bright 7 segment LED display; trip relay cum DPM with class 0.5
- User selectable CT primary from 1 A to 999 kA; 1P2W / 3P4W / 3P3W
- Individual faults can be deactivated
- Auto / manual reset; auto scroll or fixed screen
- Applications: motors (overload, locked rotor, short circuit), gensets, heating systems, broken drive belt detection, load detection
Specifications
| Nominal input current | 5 A |
|---|---|
| CT secondary | 1 A to 5 A programmable on site |
| CT primary | 1 A to 999 kA programmable on site |
| Max. continuous input current | 145% of CT secondary |
| Overload withstand | 20 x for 1 s, repeated 5 times at 5 min |
| Measuring range | Current 5 - 140% of CT secondary, frequency 40 - 70 Hz |
| Current burden | < 0.25 VA approx. per phase |
| Current / frequency | ±0.5% of nominal value / ±0.2 Hz |
|---|---|
| Delays | ±140 ms or ±5% of set delay, whichever is greater |
| Higher aux | 60 V - 300 V AC/DC (nominal 230 V AC/DC, 50/60 Hz for AC) |
|---|---|
| Lower aux | 20 V - 60 V DC / 20 V - 40 V AC (nominal 48 V DC / 24 V AC) |
| Frequency | 45 to 66 Hz |
| Burden | < 4 VA approx. |
| Current loss | 5 - 99% |
|---|---|
| Current unbalance | 2 - 20% |
| Over current | 30 - 140% (IDMT disabled), 30 - 125% (IDMT enabled) |
| Under current | 10 - 99% |
| Time multiplier setting | 0.1 - 1 |
| Trip delays | 0 - 30 s (each fault) |
| Reset delay | 0.2 - 30 s |
| Power on delay | 0.5 - 30 s |
| Reset option | Auto / manual |
| Relay control mode | De-energize / energize |
| Differential / hysteresis | 1 - 15% |
| Types | 1 CO, 2 CO or 1 CO + 1 CO |
|---|---|
| Rating | 5 A / 250 V AC / 30 V DC (resistive load) |
| Mechanical endurance | 1 x 10^7 operations |
| Electrical endurance | NO 3 x 10^4, NC 1 x 10^4 operations (1 CO / 1 CO + 1 CO); 1 x 10^5 operations (2 CO) |
| EMC | IEC 61326-1:2012, Table 2; immunity IEC 61000-4-3 10 V/m |
|---|---|
| Safety | IEC 61010-1-2010, permanently connected use |
| Installation category | 300 V CAT III / 600 V CAT II, pollution degree 2 |
| High voltage test | 2.2 kV AC, 50 Hz for 1 minute |
| Operating temperature | -10 to +55 °C |
|---|---|
| Storage temperature | -25 to +70 °C |
| Relative humidity | 0 - 90% non condensing |
| Shock | 15g in 3 planes |
| Vibration | 10 - 55 Hz, 0.15 mm amplitude |
| Enclosure | IP20 (front face only) |
| Weight | 300 g approx. |
| Order code | RISH Relay I - [1: single phase / 3: three phase] - [2000: 1 CO / 2001: 1 CO + 1 CO / 2002: 2 CO] - [HA / LA aux] |
|---|