Rishabh Relay AR-3 Three Phase Current Protection Relay
- Brand
- Rishabh
- Model number
- Relay AR-3
- Category
- Protection & Monitoring Relays
3-phase current relay for 1 - 5 A CT circuits: over current (30 - 140%), under current (10 - 95%), current unbalance, adjustable hysteresis and 0 - 10 s delay; auto / manual reset.
Price and availability on request
Key features
- Over current and under current protection plus current unbalance protection
- Nominal current set on site from 1 A to 5 A
- Potentiometer-adjustable trip points, hysteresis and time delays
- Auto / manual reset selectable on site (PRG/RST key)
- True RMS measurement (up to 15th harmonic)
- LED indication for power on, under current, over current and current unbalance
- Relay energize / de-energize on fault option
- Applications: motors (overload, locked rotor), gensets, transformer protection, ground fault protection
Specifications
| Nominal current | 1 A to 5 A settable |
|---|---|
| Max. continuous input current | 145% of maximum nominal input current |
| Overload withstand | 20 x for 1 s, repeated 5 times at 5 min |
| Current range | 5 - 140% of nominal value |
| Frequency | 40 - 70 Hz |
| Current burden | < 0.25 VA approx. per phase at nominal |
| Voltage | 60 V - 300 V AC/DC (nominal 230 V AC, 50/60 Hz) |
|---|---|
| Frequency | 45 to 66 Hz |
| Burden | < 3 VA approx. |
| Over current trip point | 30 - 140% (variable) |
|---|---|
| Under current trip point | 10 - 95% (variable) |
| Current unbalance | Trip point 20%, trip delay 5 s, hysteresis 5% (fixed); enable / disable on site |
| Hysteresis | 5 - 50% (variable) of trip point |
| Trip delay | 0 - 10 s variable for under current and over current |
| Reset delay | 1 s (fixed) |
| Power on delay | Approx. 3 s (fixed) |
| Measurement | ±2% of nominal value |
|---|---|
| Setting | ±6% of nominal value; ±0.8 s for trip delay |
| Response time | Less than 140 ms |
| Types | 1 CO or 1 CO + 1 CO, normally energized or de-energized |
|---|---|
| Rating | 5 A / 250 V AC / 30 V DC (resistive load) |
| Mechanical endurance | 1 x 10^7 operations |
| Electrical endurance | 1 x 10^5 operations |
| Operating temperature | -10 to +55 °C |
|---|---|
| Storage temperature | -25 to +70 °C |
| Relative humidity | 0 - 90% non condensing |
| Shock | 15g in 3 planes |
| Vibration | 10 - 55 Hz, 0.15 mm amplitude |
| Enclosure | IP20 (front face only) |
| Weight | 175 g approx. |
| Safety | IEC 61010-1-2010 |
|---|---|
| Installation category | CAT III, pollution degree 2 |
| High voltage test | 2.2 kV AC, 50 Hz for 1 minute between all electrical circuits |
| Order code | AR-3-[1 / 2 relays]-[1: energized / 2: de-energized], e.g. AR-3-2-1 |
|---|