Rishabh PFC 08 Power Factor Controller, 96 x 96 mm
- Brand
- Rishabh
- Model number
- PFC 08
- Category
- Protection & Monitoring Relays
APFC relay (96 x 96 mm) for capacitor bank switching with 4, 6 or 8 control outputs plus alarm relay; auto-initialisation, test run, energy and harmonics up to 31st; Modbus / RTC optional.
Price and availability on request
Key features
- Control outputs: 4, 6 or 8
- Auto-initialisation: detects number of capacitor banks, bank kVAr value and phase correction angle
- Bank kVAr programmable as direct value, control series or auto-detected value
- Intelligent bank switching for equal use of capacitors; capacitor health monitoring
- Each output can be set to permanently ON, permanently OFF or auto
- Manual mode for diagnosis and test run to measure connected bank kVAr
- Alarm relay for high / low voltage, under / over current, over temperature, frequency faults, voltage / current harmonics, under and over compensation
- Measures V, A, Hz, power, energy (import / export), demand, THD and individual harmonics up to 31st
- High contrast 16 x 2 LCD with backlight
- Optional Modbus (RS485) output and RTC
Specifications
| Number of outputs | 4, 6 or 8 (up to 8 max.) |
|---|---|
| Alarm output | 1 |
| Target PF range | 0.8 lead to 0.8 lag |
| Switching threshold | 30 to 100% |
| Connecting / disconnecting time | 10 to 1800 s |
| Discharge time | 60 to 1800 s |
| Nominal input voltage | 240 V AC |
|---|---|
| Voltage measuring range | 30 - 550 V AC |
| Nominal input current | 1 A / 5 A AC; CT primary 1 A up to 9999 A |
| Current range | 3 mA starting, 10 mA operating, max. 6 A |
| Frequency | 40 - 70 Hz |
| Voltage | 110 V AC to 550 V AC, 40 to 70 Hz |
|---|
| Voltage / current / auxiliary | < 0.2 VA per phase / < 0.6 VA per phase / < 10 VA |
|---|
| Voltage, current | ±0.5% of nominal value |
|---|---|
| Frequency | ±0.15% of mid frequency |
| Power and energy | ±1.0% of nominal value |
| THD | ±1.0% of applied value |
| Under / over voltage | 85% (75 - 90%) / 115% (105 - 115%) of V nom |
|---|---|
| Under / over frequency | 6% (2 - 10%) |
| Under / over current | 2% (1 - 3%) / 110% (60 - 120%) of CT primary |
| V-THD / I-THD | 7% (1 - 25% / 1 - 99%) |
| Compliance | IEC 61326-1:2012, IEC 62053-21, IEC 61010-1-2010; installation category III |
|---|---|
| High voltage test | 2.2 kV AC, 50 Hz for 1 minute |
| Operating temperature | -10 to +60 °C |
|---|---|
| Storage temperature | -20 to +65 °C |
| Relative humidity | 0 - 90% non condensing |
| Front protection | IP 54 (IEC 60529) |
| Dimensions | 96 x 96 x 59 mm without add-on card, 96 x 96 x 75 mm with add-on card |
| Order code | PF40-A1H[4 / 6 / 8 relays]A[R / Z Modbus][R / Z RTC]0000RI, e.g. PF40-A1H8ARR0000RI |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.