Rishabh LM1360 RJ12 Load Manager Multifunction Meter, RJ12 CT Input
- Brand
- Rishabh
- Model number
- LM1360 RJ12
- Category
- Power and Energy Meters
LM1360 load manager for RJ12 (100 mA) plug-and-play CTs: class 1 energy, harmonics to 31st, optional relays, RTC, data logging, USB, RS485, Ethernet or BACnet.
Price and availability on request
Key features
- True RMS measurement on 3P4W, 3P3W and 1P2W networks; more than 85 parameters
- Import / export active, reactive and apparent energy; quadrant-wise reactive energy
- THD and individual harmonics up to 31st for voltage and current
- Optional relay outputs as pulse, limit (alarm), timer or remote control via Modbus
- RJ12 connector for plug-and-play external CTs
- Optional RTC relay, data logging and isolated USB interface
Specifications
| Nominal voltage | 100 VLL to 600 VLL (programmable on site) |
|---|---|
| PT primary | 100 VLL to 1200 kVLL, programmable on site |
| Nominal current | 100 mA via RJ12 plug-and-play CT |
| CT primary | 1 A to 9999 A, programmable on site |
| Active energy | Class 1 as per IEC 62053-21 |
|---|
| Auxiliary supply | Higher 100-550 V AC/DC (230 V nominal) or lower 12-60 V AC/DC |
|---|
| Relay rating | 250 V AC, 5 A AC |
|---|
| Options | RS485 + 2 pulse outputs, Ethernet, Ethernet + data logging, RS485 + data logging + USB, BACnet |
|---|
| Mounting | Panel mounted, 96 x 96 mm |
|---|---|
| Enclosure | IP54 front, IP20 terminals |
| Operating temperature | -20 to +70 °C |
|---|
| Order code | MA4L-430101[R / E / D / U / B / Z][H / L]10000, e.g. MA4L-430101RH10000 |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.