Rishabh EQ 48 Moving Iron AC Ammeter / Voltmeter, 90°, 48 x 48 mm
- Brand
- Rishabh
- Model number
- EQ 48
- Category
- Panel Meters
Moving iron panel meter, 48 x 48 mm, 90° scale: true RMS AC voltage or current, class 1.5, interchangeable scales, CT / PT operated versions; UL 94 V-0 polycarbonate case.
Price and availability on request
Key features
- True RMS AC voltage or current, practically independent of waveform
- Scale interchangeability: dials slide out and in from the front
- Near linear scale above 10% of full scale
- Ammeter over range: none, 2 times or 6 times nominal current
- Glass filled polycarbonate case, flame retardant and drip proof (UL 94 V-0)
- Knife edge pointer; easily replaceable glass and bezel
- Easy installation with swivel screws; several meters can share one cut-out (mosaic mounting)
Specifications
| Measured quantity | AC voltage or current |
|---|---|
| Standard ranges | AC voltage 6 V ... 600 V (750 V except EQ 48); AC current 100 mA ... 60 A (100 A except EQ 48); for use on .../1 A or .../5 A CT and .../100 V or .../110 V PT |
| Frequency range | 15 ... 100 Hz (voltage), 15 ... 400 Hz (current) |
| Accuracy class | 1.5 (IS 1248 / IEC 51) |
| Power consumption | Voltmeters < 4.5 VA; ammeters < 15 A < 0.5 VA, > 15 A < 0.8 VA |
| Pointer deflection | 0 ... 90° |
|---|---|
| Scale length | 41 mm |
| Rated insulation / proof voltage | 660 V / 2 kV |
|---|---|
| Installation category | 300 V CAT III |
| Operating temperature | -5 ... +50 °C |
|---|---|
| Storage temperature | -40 ... +70 °C |
| Front size | 48 x 48 mm |
| Panel cut-out | 45 x 45 mm |
| Weight (approx.) | 0.1 kg |
| Case | Moulded square case, glass filled polycarbonate (UL 94 V-0) |
| Enclosure | IP 52 case; IP 20 terminals with back cover |
| Options on order | Antiglare glass; red, yellow, blue or white bezel; blank or special dials; red or green markings |
|---|
| Contents | Meter with full sized polycarbonate back cover (terminal protection) |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.