Rishabh EM 2340DS Dual Source Energy Meter with Backlit LCD
- Brand
- Rishabh
- Model number
- EM 2340DS
- Category
- Power and Energy Meters
Rish EM 2340DS dual source energy meter: separate utility and generator energy and parameters for 3 phase or 1 phase networks, backlit LCD, optional RS485 and pulse / limit outputs.
Price and availability on request
Key features
- Measures utility and generator parameters separately
- True RMS; import / export active, reactive and apparent energy
- On site programmable CT and PT ratios
- Backlit LCD showing 3 parameters
- Run hour, on hour and interruptions
Specifications
| Nominal voltage | 100 VL-L to 500 VL-L (57.7 VL-N to 290 VL-N), programmable |
|---|---|
| Nominal current | 1 A / 5 A AC, programmable |
| Energy | As per IEC 62053-21 and IEC 62053-23 |
|---|
| Auxiliary supply | 60-300 V AC/DC or 20-60 V DC / 20-40 V AC |
|---|
| Option | RS485 Modbus, baud rate up to 38.4 kbps |
|---|
| Option | 1 or 2 pulse / limit relays |
|---|
| Enclosure | IP50 front |
|---|
| Operating temperature | -10 to +55 °C |
|---|
| Order code | RISH EM 2340-[3 / 1]-[EA / LA]-[R / Z]-[P1 / P2 / NP], e.g. RISH EM 2340-3-EA-R-P2 |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.