Rishabh ELPR Smart+ Earth Leakage Protection Relay (Smart+)
- Brand
- Rishabh
- Model number
- ELPR Smart+
- Category
- Protection & Monitoring Relays
DIN-rail earth leakage relay with CBCT input: In 30 mA - 30 A and trip delay 0 - 10 s set by potentiometer, CBCT open detection, bar graph LEDs; DIP switches for auto re-closure, fail-safe or alarm relay and main relay configuration.
Price and availability on request
Key features
- Leakage current set by front potentiometer: 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A, 5 A, 10 A, 20 A or 30 A
- Trip delay set by potentiometer: 0, 0.06, 0.15, 0.25, 0.5, 0.8, 1, 2.5, 5 or 10 s (0 = instantaneous)
- CBCT connection fault detection (PON LED blinks)
- DIP switches: auto re-closure (3 reset attempts) or manual reset, relay 2 as fail-safe or alarm relay, main relay energized or de-energized
- True RMS, Type A earth leakage relay (up to 15th harmonic)
- Bar graph LEDs show leakage at 30%, 45%, 60% and 75% of set In
- Test and reset keys plus remote reset contacts
- Wide auxiliary supply: 20 - 60 V DC / 20 - 40 V AC or 60 - 300 V AC/DC
- DIN-rail mount 2U flame retardant housing
- Applications: motor protection, mining equipment, industrial and substation premises
Specifications
| Leakage current (In) | 30 mA to 30 A (Type A), via CBCT |
|---|---|
| Tripping operating range | 80% to 100% of In |
| Alarm operating range | > 50% of In |
| Reset hysteresis | 15% of trigger value |
| Power on / reset delay | Approx. 1 s |
| Options | L: 20 - 60 V DC / 20 - 40 V AC; M: 60 - 300 V AC/DC |
|---|---|
| Frequency | 45 to 66 Hz |
| Burden | < 4 VA approx. |
| Leakage current | 5% of full scale |
|---|---|
| Trip delay | 5% of set trip time or 50 ms, whichever is greater |
| Instantaneous trip | < 25 ms for leakage current greater than 5 x set In (not for 30 A range) |
| Relay 1 (ELR) | 1 NO + 1 NC (1 CO), energized / de-energized by DIP switch |
|---|---|
| Relay 2 | 1 NO, alarm or fail-safe by DIP switch |
| Rating | 5 A / 250 V AC or 30 V DC |
| Mechanical endurance | 1 x 10^7 operations |
| Electrical endurance | 5 x 10^4 operations (resistive load) |
| Operation | Non potential free (approx. 12 V DC), isolated contacts for remote resetting |
|---|
| Compliance | IEC 61326-1:2012, IEC 60947-2 Annex M, IEC 61010-1-2001; IEC 60755 optional |
|---|---|
| Installation category | III 300 V |
| High voltage test | 2.2 kV AC, 50 Hz for 1 minute |
| Operating temperature | -20 to +65 °C |
|---|---|
| Storage temperature | -40 to +70 °C |
| Relative humidity | 0 - 90% non condensing |
| Enclosure | IP40 front face, IP20 terminals |
| Housing dimensions | 90 x 65 x 35 mm as per DIN 43880 |
| Weight | 125 g approx. |
| Order code | ELR2-[L/M]-AR (L: 20 - 60 V DC / 20 - 40 V AC, M: 60 - 300 V AC/DC aux.) |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.