Rishabh 256-PHV Combined Under / Over Voltage & Frequency Relay

Brand
Rishabh
Model number
256-PHV

Generator and supply monitor in one: under / over voltage (75 - 125%) and under / over frequency setpoints with adjustable delays of 1 - 30 s; for 50, 60 or 400 Hz systems.

Price and availability on request

Request a quote

Sent with the product details: Rishabh 256-PHV Combined Under / Over Voltage & Frequency Relay.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • User-adjustable setpoints for voltage and frequency
  • Adjustable time delay
  • Internal differential (factory settable)
  • LEDs show the relay condition
  • Energize / de-energize function swapping on request
  • 2 pole relay contacts
  • Auto reset
  • Applications: gensets (AVR and governor), motors, UPS and standby supplies

Specifications

Voltage
Nominal voltage100, 110, 120, 220, 230, 240 V
RangeOver voltage 100 to 125%, under voltage 75 to 100%
DifferentialFixed internally 1% to 10% (specify)
Time delayAdjustable between 1 and 30 s
Frequency
Ranges40-60 Hz (50 Hz), 50-70 Hz (60 Hz) or 360-440 Hz (400 Hz)
DifferentialFixed internally 0.1 Hz to 3 Hz (10 Hz for 400 Hz unit)
Time delayAdjustable between 1 and 30 s
Setpoint
Repeatability> 0.5% of full span
Input
Voltage withstand1.2 x rating continuously, 1.5 x rating for 10 s (BS 6253)
Output relay
TypeD.P. changeover
RatingA.C. 240 V 5 A non-inductive; D.C. 24 V 5 A resistive
Operations0.2 million at the above loads
ResetAutomatic
General
Operating temperature0 °C to +60 °C
Storage temperature-20 °C to +70 °C
Temperature co-efficient0.05% per °C
Interference immunityElectrical stress surge withstand and non function to ANSI/IEEE C37 90a
EnclosureDIN-rail with wall mounting facility, flame retardant polycarbonate / ABS
Enclosure integrityIP 50
Dimensions150 mm wide x 70 mm high x 112 mm deep
WeightApprox. 1 kg

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.