Multispan PSC 9044U-M1 4-Channel Scanner with USB Data Logger
- Brand
- Multispan
- Model number
- PSC 9044U-M1
- Category
- Process Indicators & Scanners
4-channel scanner for analog, thermocouple and RTD inputs, with four changeover relays, RS-485 Modbus and USB data logging. 100-270 V AC/DC supply.
Price and availability on request
Key features
- 4 Channel Scanner
- Analog- 0 - 10V DC, 0 - 20mA DC, 4 - 20mA DC (-999 To 9999)
- Thermocouple: J, J.1, K, K.1, PT-100, PT.1, R, S, E, N, T, B, C, L, U
- RTD: PT-100 (-200 to 600°C), PT.1 (-199.9 to 600.0°C)
- 4 relay 1C/O, (NO-C-NC)
- ModBus RS-485
- USB Data Logging Facility
- Supply voltage: 100V To 270V AC/DC
Specifications
| Display | UPPER: 4 Digit 7 seg 0.70”, WHITE LED Display; LOWER: 4 Digit 7 seg 0.50”, GREEN LED Display |
|---|---|
| Size (mm) | 98 (H) X 98 (W) X 76 (D) mm |
| Panel Cutout (mm) | 92 (H) X 92 (W) |
| Inputs and Range | Thermocouple; J -200 to 800°C; J.1 -200.0 to 800.0°C; K -200 to 1200°C; K.1 -200.0 to 950.0°C; R 0°C to 1800°C; S 0°C to 1850°C; E 0°C to 600°C; N -200°C to 1350°C; T -200°C to 400°C; B 150°C to 1800°C; C 0°C to 2350°C; L -200°C to 800°C; U -200°C to 800°C; RTD; PT-100/3W -200 to 600°C; PT.1/3W -199.9 to 600.0°C |
| Accuracy | J, J.1, K, K.1, R, S, PT, PT.1 : ±0.25% Full Scale ± 1 Digit; T, E, N, B, C, L, U : ±0.5% Full Scale ± 1 Digit; ANALOG I/P : ±0.25% Full Scale ± 1 Count |
| Output | 4 Relay (NO-C-NC) 1C/O 5A@230V AC, 5A for resistive load; USB Data Logging Facility with RS-485 RTU MODBUS |
| Power Supply | 100 to 270V AC/DC,50/60 Hz, Approx 6VA |
| Operating Temperature | 0°C To 55°C |
| Relative Humidity | Up to 95% RH Non Condensing |
| Protection Level | IP-65 (Front side) As per IS/IEC; 60529 : 2001 |
| Typical uses | Pharma & Chemical Industry application, Generator Monitoring & Protection, Machine Condition Monitoring, As a distributed I/O module for interface with PLC/DCS/SCADA, Compressor/Pump/DG set monitoring Remote terminal unit (RTU) For SCADA, Laboratory Equipment Monitoring |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.