Multispan PS24-6.5A-P Power Supply 24V 6.5A, Plastic Body
- Brand
- Multispan
- Model number
- PS24-6.5A-P
- Category
- DIN-Rail Power Supplies
DIN-rail switching power supply, 24 V DC at 6.5 A (156 W) from a 100-270 V AC input, in a polycarbonate case, with overload, over-voltage, short-circuit and over-temperature protection.
Price and availability on request
Key features
- Power 156W
- Input Voltage : 100-270V AC
- Output Voltage : 24V DC
- Efficiency <89%@230VAC
- Material: Polycarbonate (PC)
- Protection Parameter : Output Overload, Output Over Voltage , Output short circuit, Over Temperature
Specifications
| Supply Voltage | 100 to 270V AC±10%,(L-N); 127 to 350V DC |
|---|---|
| Frequency Range | 50 / 60Hz |
| AC Current (TYP.) | 2.9A@100V AC; 1.2A@270V AC |
| Efficiency (TYP.) | <89%@230VAC |
| Start UP time | <1 sec@230V AC &; <3 sec@100VAC (Full Load) |
| Output Voltage | 24-28V DC |
|---|---|
| Output Current | 6.5A at 24V; 5.57A at 28V |
| Ripple & noise | <1% of V out |
| Line & Load Regulation | ±1% |
| Hold UP Time | <60ms at 230V AC &; >15ms at 100V AC (Full Load) |
| LED 1 | Power On |
|---|
| Input Fuse | 5A-250V AC Internal |
|---|---|
| Output Over Load | 110% to 120% of rated output Current protection Protection Type : hiccup mode; recover automatically after fault condition is removed |
| Output Short Circuit | Hiccup mode when output is shorted; Recovers automatically after fault condition is removed. |
| Output Over Voltage | SMPS Latches off if output voltage exceeds the specified output voltage limit. |
| Over Temperature | SMPS Latches off if the transformer temperature exceeds 120°C |
| Isolation between Input and Output | 2.5 KV |
| Mounting Type | Din Rail Mount |
|---|---|
| Size | 110 (H) x 48 (W) x 111 (D) |
| Material Body | Polycarbonate (PC) |
| Terminal Screw Size | M3 |
| Screw Torque (N.m) | 0.5 |
| Wire Gauge (AWG) | 28-12 |
| Typical uses | Robotics, Elevators, Automation panel, Special purpose machine |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.