Multispan AVH-14-M1 Multifunction Meter with Separate kWh Display

Model number
AVH-14-M1

Class 0.5 panel multifunction meter for single and three-phase systems with a separate kWh display, PT primary up to 520 kV, pulse output and RS-485 Modbus.

Price and availability on request

Request a quote

Sent with the product details: Multispan AVH-14-M1 Multifunction Meter with Separate kWh Display.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • 1Ø-2W, 3Ø-3W/4W Selectable
  • Separate Display for KWH Reading
  • Primary Voltage 100V to 520kVAC
  • Secondary Voltage 100V to 520V AC
  • Pulse & RS-485 MODBUS Communication
  • Accuracy Class 0.5

Specifications

Parameter Specification
Input Signal3Ø-3/4Wire / 1Ø 2Wire
CT Primaryup to 6000A (Programmable)
CT Secondary5 Amp/1 Amp selectable
PT Primary100V to 520kV (Programmable)
PT Secondary100V to 520V (L-L) (Programmable)
PF Avg. & Per Phase0.100 - 1.000
Frequency (Hz)45.00 - 60.00 Hz
Load hours9999.59 Hrs/Min
No load hours9999.59 Hrs/Min
RPM3600 RPM @ 60 Hz & 2 pole
Power
kW Total0.000 - 9999 MW
kW Per Phase0.000 - 9999 MW
kVA Total0.000 - 9999 MVA
kVA Per Phase0.000 - 9999 MVA
kVAr Total0.000 - 9999 MVAr
kVAr Per Phase0.000 - 9999 MVAr
Energy
WH Total000.000 - 999999 MWh
Vah Total000.000 - 999999999.999 MVAh
Varh Total000.000 - 999999999.999 MVArh
Display and Keys
Display Lower4 Digit, 3 Line 7 Seg 0.39”,RED
KeyPROGRAM, VAF, POWER, ENERGY
Auxiliary Supply
Supply voltage100 to 270V AC/DC, 50/60Hz
Power consumption (VA RATING)Approx 4 VA @ 230V AC MAX
Communication
CommunicationRS-485 MODBUS
Accuracy
AccuracyClass 0.5 (Standard)
Environment
Operating Temp0°C to 55°C
Relative HumidityUpto 95% RH (non-condensing)
Protection Level (AS Per Request)IP-65 (Front side) As per IS/IEC 60529 : 2001
Dimension
Size (mm)96 (H) x 96 (W) x 54 (D)
Panel Cutout (mm)92 (H) x 92 (W)
Applications
Typical usesControl & Relay Panel, Energy Management System, DG Set Panels, LT / HT Panel, Power Control Center Panels, Motor Control Center Panels
Order codes
AVH-14-E3-N1Voltage Network Selection :3Ø3W/4W, 1Ø2W; Primary Voltage : 100V to 520KV AC; Secondary Voltage : 100V to 520V AC; Current CT Primary : Upto 6000A; CT Secondary : 5A/1A Selectable; Supply 100 to 270V AC/DC
AVH-14-E3-N3Voltage Network Selection :3Ø3W/4W, 1Ø2W; Primary Voltage : 100V to 520KV AC; Secondary Voltage : 100V to 520V AC; Current CT Input: 30A with DIN 30AX CT; Supply 100 to 270V AC/DC
AVH-14-E3-N2Voltage Network Selection :3Ø3W/4W, 1Ø2W; Primary Voltage : 100V to 520KV AC; Secondary Voltage : 100V to 520V AC; Current CT Input: 60A with DIN 60AX CT; Supply 100 to 270V AC/DC
AVH-14-E3-N4Voltage Network Selection :3Ø3W/4W, 1Ø2W; Primary Voltage : 100V to 520KV AC; Secondary Voltage : 100V to 520V AC; Current CT Input: 100A with DIN 100AX CT; Supply 100 to 270V AC/DC

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.