Minilec S2 CMR1 Motor / Pump Protection Relay
- Brand
- Minilec
- Model number
- S2 CMR1
- Category
- Motor Protection Relays
Minilec S2 CMR1 motor / pump protection relay with 2 CO output. Typical uses: air -conditioning & refrigeration machines, crusher motors , mining m/c, screw compressors.
Price and availability on request
Key features
- Overload & Dry Run, Unbalance
- Auto/Manual Reset
- Phase Failure, Phase Sequence
- Adjustable Trip Settings
- Selectable Overload Characteristics
- 2 CO Output Relay
- Microcontroller Design
- SMD Technology
Specifications
| Output Relay Contact | 2 CO |
|---|---|
| Input | From S2 CTS 1 |
| Resetting | Auto / Mannual |
| Approx Weight | 140 gms |
| Note | Wherever not specified Contact Rating: 5A @ 230 V AC (resistive) |
| Auxiliary | 100-120/220-240/415V AC ± 20%, 48 - 63 Hz 24V DC+10%-15% |
|---|
| Phase to phase unbalance | 50% of Motor Current (fixed) |
|---|---|
| Under Current (Dry Run) | 40% to 80% ± 5% of Set Current (Adjustable with Bypass Facility) |
| Overload | As per IDMTL Characteristics |
| On phase failure | 4 Sec ± 1% Sec (Fixed) |
|---|---|
| overload | As per IDMTL Characteristics 2/5/10 Sec. (Selectable) 2/5/10 Sec. (Selectable) |
| Overall (L x W x D) | 90 x 35 x 60 |
|---|---|
| Mounting (L x W) | 35 mm Rail Mounting |
| Applications | Air -Conditioning & Refrigeration Machines, Crusher Motors , Mining M/c, Screw Compressors, End Users, Lift , Elevators, Hoist & Cranes |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.