Minilec PROTOCOM 4 Twin AC Controller

Brand
Minilec
Model number
PROTOCOM 4

Minilec PROTOCOM 4 twin AC controller, for 240 V AC ±20% (L1, L2 & N) supply. Typical uses: single phase twin AC unit control, energy saving by optimal use of AC. units, ATM machine.

Price and availability on request

Request a quote

Sent with the product details: Minilec PROTOCOM 4 Twin AC Controller.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Specifications

Specifications
System Supply240 V AC ±20% (L1, L2 & N)
Frequency50 / 60 Hz ± 3%
Output Relay Contacts1 NO + 1 NO + 1 NO + 1 NO
Output Contact Rating30 Amp. @ 240 V AC (RLY 1 & RLY 2) 5 Amp. (RLY 3 & RLY 4)
Current Setting1-20 Amp (Variable)
Power ON Delay2 - 600 sec.
Cyclic Time Delay3 Min. To 24 Hrs
EnclosureSheet Metal fabricated and powder coated
Weight1100 gms.
Setting Keys4 nos. of Front Keys
LED Indication
AC ONGREEN
AlarmRED
UV / OVRED
UC / OCRED
Dimensions (mm)
Overall (L x W x D)141 X 193.9 X 72
Mounting117 X 169.5
Logic Setting
Logic # 1SINGLE AC OPERATION ONLY IN ALTERNATE MODE
Logic # 2SINGLE OR BOTH AC OPERATIONS BASED ON TEMP. RISE IN ALTERNATE MODE
Settings and ratings
Trip SettingUnder Voltage 120 - 210 V AC, Over Voltage 240 - 300 V AC, Over Load 5 - 20 Amp. (Settable by Keys & Display) (Default Set - 20 A), Over Temperature 22 - 45 ° C (Settable by Keys & Display) (Default Set - 35° C)
Hysteresis for Auto ResetUnder Voltage 6 VAC ± 3 VAC, Over Voltage 6 VAC ± 3 VAC, Over Temperature 1° C - 10° C (Default - 3° C)
Trip Time DelayUnder Voltage 5 sec., Over Voltage 5 sec., Over Load 2 - 5 sec., Over Temperature 2 - 900 sec. (Default Set - 600 sec)
Product
ApplicationsSingle Phase Twin AC unit control, Energy Saving by optimal use of AC. Units, ATM Machine

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.