Minilec F3 MPR1 Microprocessor Based Motor Protection Relay
- Brand
- Minilec
- Model number
- F3 MPR1
- Category
- Motor Protection Relays
Minilec F3 MPR1 microprocessor based motor protection relay, for 220-440 V AC ±20% supply. Typical uses: crane motors, AHU fan /pump motors, heavy duty motors.
Price and availability on request
Key features
- Microcontroller based
- Sensing, current and temperature
- Protecting against Phase Failure
- Unbalance
- Locked rotor, Adjustable trip Setting for UC/OC, O/L
- Phase sequence, Overloading
- Winding over temperature
- Over current/Short circuit
- Auto/Manual resetting
- Locked rotor & earth fault
- On delay & start-up delay adjustable
- 2x1CO output relays and serial communication port
Specifications
| Output Relay Contact | 2 CO (5 Amp .230 V AC reistive) |
|---|---|
| Serial Communication | Provision of RS485 Output |
| Input | External CTS ( CT1/CT2.5/CT5/CT20/CT50 ) |
| Display | 16x2 (Back lit LCD Display) |
| Operating Temperature | 0°C to 60°C |
| Humidity | Upto 95% Rh |
| Enclosure | F3 Series ABS |
| Approx Weight Unit | 400 gms |
| Note | Wherever not specified Contact Rating: 5A @ 230 V AC (resistive) |
| System | 220-440 V AC ±20% |
|---|---|
| Auxiliary | 90-270 V AC/DC (45-65 Hz), 24 V DC |
| Overall (L x W x D) | 96 x 96 x 80 |
|---|---|
| Mounting (L x W) | Panel Mounting - 92 x 92 |
| Over load Trip Setting As per IDMTL Char | Setting Range 2/5/10/15/20 Sec, LCD Display Over Load, Resetting Mode Manual |
|---|---|
| Unbalance Trip Setting | Setting Range 20%-60%, Trip Delay 1-10 Sec, LCD Display Current Unbalanced, Resetting Mode Manual/Multi Attempt |
| Phase Failure | Trip Delay 1-10 Sec, LCD Display Current S.P, Resetting Mode Manual |
| Reverse Phasing | Trip Delay Instant, LCD Display Phase Reversal, Resetting Mode Manual |
| Under Current | Setting Range 30%-90%, Trip Delay 1-60 Sec, LCD Display Under Current, Resetting Mode Manual/Multi Attempt |
| Over Current | Setting Range 300%-800%, Trip Delay 2-25 Sec, LCD Display Over Current |
| Lock Rotor | Setting Range 200%-500%, Trip Delay 1-10 Sec, LCD Display Rotor Lock, Resetting Mode Manual |
| Earth Fault Setting | Setting Range 10%-100%, Trip Delay 0.5 - 10 Sec, LCD Display Earth Fault, Resetting Mode Manual |
| Over Temp. | Setting Range 70°C to 180°C, Trip Delay 1-20 Sec, LCD Display Sensor Fail Motor Temp. High, Resetting Mode Auto/ Manual |
| Applications | Crane Motors, AHU Fan /Pump Motors, Heavy Duty Motors, Screw Compressors, HT Motors, Pump protection, Pump House Automation |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.