| CT Range | Range 35-175 Amp, Resolution 1 Amp, Fact setting 100 Amp |
|---|
| Over Load | Range Above 115 % of Set Value, Trip delay Range IDMT class 2,5,10,15,20, 30 sec, Factory setting 2 sec, By Pass Facility Yes, Reset type Auto/ Manual |
|---|
| Start up delay | Range 0 - 60 sec, Resolution 1 sec, Fact setting 10 sec |
|---|
| Under Current | Range 30 - 174Amp, Resolution 2 Amp, Fact setting 50 Amp, Trip delay Range 1- 60 sec, Factory setting 5 sec, By Pass Facility Yes, Reset type Auto/ Manual |
|---|
| Over Current | Range 110 - 350%, Resolution 5%, Fact setting 200%, Trip delay Range 1 -10 sec, Factory setting 2 sec, By Pass Facility Yes, Reset type Auto/ Manual |
|---|
| Current Unbalance | Range 20 - 60 %, Resolution 5%, Fact setting 50%, Trip delay Range 4 sec Fixed (+/-1 sec), Factory setting 4 sec, By Pass Facility Yes, Reset type Auto/ Manual |
|---|
| Current Single Phasing | Range Yes, Trip delay Range 4 sec Fixed (+/-1 sec), Factory setting 4 sec, By Pass Facility Yes, Reset type Auto/ Manual |
|---|
| Reverse Phase | Range Yes, Trip delay Range Instant ( < 2 sec), By Pass Facility Yes (Password protected), Reset type Auto/ Manual |
|---|
| Rotor Lock | Range 200- 800%, Resolution 50%, Fact setting 700%, Trip delay Range Instant ( < 2 sec), By Pass Facility Yes, Reset type Auto/ Manual |
|---|
| Earth Fault | Range 10- 100%, Resolution 10%, Fact setting 30%, Trip delay Range 0.5-10 sec, Factory setting 0.5 sec, By Pass Facility Yes, Reset type Auto/ Manual |