| Set Current (FLC){Ext. CT not applicable } | Range 3A to 10A(6 Turns Ext.), Resolution 1 Amp |
|---|
| Over Load | Range Fixed @ 110% of Set Value, Trip delay Range IDMTL class 2,5,10,15,20,30 sec OR Fixed Definite Trip Delay 1 to 30sec Selectable, Factory setting IDMT2 sec, By Pass Facility Yes, Reset type Auto/Manual |
|---|
| Start up delay | Range 0-60 sec, Resolution 1 sec, Fact setting 10 sec |
|---|
| Under Current | Range 30 - 90%, Resolution 5%, Fact setting 50%, Trip delay Range 1- 60 sec, Factory setting 5 sec, By Pass Facility Yes, Reset type Auto/ Manual |
|---|
| Lock Rotor | Range 200-800%, Resolution 10%, Fact setting 200%, Trip delay Range 1 -10 sec, Factory setting 2 sec, By Pass Facility Yes, Reset type Auto/ Manual |
|---|
| Current Unbalance | Range 20 - 60 %, Resolution 5%, Fact setting 50%, Trip delay Range 4 sec Fixed (+/-1 sec), Factory setting 4 sec, By Pass Facility Yes, Reset type Auto/ Manual |
|---|
| Current Single Phasing | Range Yes, Trip delay Range 4 sec Fixed (+/-1 sec), Factory setting 4 sec, By Pass Facility Yes, Reset type Auto/ Manual |
|---|
| Reverse Phase | Range Yes, Trip delay Range Instant (1 sec), Factory setting Instant (1 sec), By Pass Facility Yes (Password protected), Reset type Auto/ Manual |
|---|
| Stalling | Range 200- 800%, Resolution 50%, Fact setting 700%, Trip delay Range Instant (1 sec), Factory setting Instant (1 sec), By Pass Facility Yes, Reset type Auto/ Manual |
|---|
| Earth Fault (Optional) | Range 10- 100% (OF 5A/1A), Resolution 10%, Fact setting 30%, Trip delay Range 0.5-10 sec, Factory setting 0.5 sec, By Pass Facility Yes, Reset type Auto/ Manual |
|---|
| Short Circuit | Range 600-999%, Resolution 50%, Fact setting 800%, Trip delay Range Instant (1 sec), Factory setting Instant (1 sec), By Pass Facility Yes, Reset type Auto/ Manual |