Minilec D3 DMPR1 Microprocessor Based Motor Protection Relay

Brand
Minilec
Model number
D3 DMPR1

Minilec D3 DMPR1 microprocessor based motor protection relay with 2 CO output, for 380 - 440 V AC ± 20%, 45 - 55 Hz. supply.

Price and availability on request

Request a quote

Sent with the product details: Minilec D3 DMPR1 Microprocessor Based Motor Protection Relay.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Micro controller based
  • Sensing current
  • Protecting against Phase Failure, Unbalance, Phase sequence, overloading, Over current/Short circuit, locked rotor,
  • Auto/Manual resetting
  • Adjustable trip settings for UC/OC, O/L, Locked rotor & earth fault
  • Start-up delay adjustable
  • 2x1CO output relays and last ten faults logging

Specifications

Specifications
Internal CT For D3 DMPR15 Amp or 20 Amp. or 50 Amp
Output Contacts2 CO
Fault MemoryLast 10 faults
ResetAuto / Manual
Display8 X 2 AN LCD
Weight400 + 150 GMS (Approx)
Overall D3 encl71 (H) x 100 (L) x 111 (D)
Overall (H x L x D)48 (H) x 96 (L) x 55 (D)
Mounting (L x W)35 mm DIN Rail
Supply Voltage
System Supply380 - 440 V AC ± 20%, 45 - 55 Hz.
Auxiliary Supply90 - 270 V AC / DC, 415 V AC
Settings and ratings
Ext. CTRange 50 - 600, Resolution 5 Amp, Fact setting 100 Amp
Set current (FLC)Range 30 to 100 % of FLA, Resolution 1 Amp, Fact setting 5 Amp
Over LoadRange Above 110 % of Set Value, Trip delay Range IDMT class 2,5,10,15,20, 30 sec, Factory setting 2 sec, By Pass Facility Yes, Reset type Auto/ Manual
Start up delayRange 0 - 60 sec, Resolution 1 sec, Fact setting 10 sec
Under CurrentRange 30 - 90%, Resolution 5%, Fact setting 50%, Trip delay Range 1- 60 sec, Factory setting 5 sec, By Pass Facility Yes, Reset type Auto/ Manual
Over CurrentRange 110 - 350%, Resolution 5%, Fact setting 200%, Trip delay Range 1 -10 sec, Factory setting 2 sec, By Pass Facility Yes, Reset type Auto/ Manual
Current UnbalanceRange 20 - 60 %, Resolution 5%, Fact setting 50%, Trip delay Range 4 sec Fixed(+/- 1 sec), Factory setting 4 sec, By Pass Facility Yes, Reset type Auto/ Manual
Current Single PhasingRange Yes, Trip delay Range 4 sec Fixed(+/- 1 sec), Factory setting 4 sec, By Pass Facility Yes, Reset type Auto/ Manual
Reverse PhaseRange Yes, Trip delay Range Instant ( < 2 sec), By Pass Facility Yes (Password protected), Reset type Auto/ Manual
StallingRange 200- 800%, Resolution 50%, Fact setting 700%, Trip delay Range Instant ( < 2 sec), By Pass Facility Yes, Reset type Auto/ Manual
Earth FaultRange 10- 100%, Resolution 10%, Fact setting 30%, Trip delay Range 0.5-10 sec, Factory setting 0.5 sec, By Pass Facility Yes, Reset type Auto/ Manual
Short CircuitRange 600 - 999%, Resolution 50%, Fact setting 800%, Trip delay Range Instant(< 2sec), By Pass Facility Yes, Reset type Auto/ Manual

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.