Minilec D2 PTC1 Current Transducer

Brand
Minilec
Model number
D2 PTC1

Minilec D2 PTC1 current transducer. Typical uses: speed control feedback application, metering & relay panels for substations.

Price and availability on request

Request a quote

Sent with the product details: Minilec D2 PTC1 Current Transducer.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Current transducer
  • Input AC Current
  • Output (DC) single or dual
  • Accuracy 0.5%

Specifications

Specifications
Power Consumption3.5 VA - AC, 4 VA - DC
DC Output (Single / Dual)0 - 1 mA, 0 - 10 mA, 0 - 20 mA, 4 - 20 mA, 0 - 5 V, 0 - 10V DC Other optional on request
No of Signal OutputSingle (Optional Dual Output)
Response TimeLess than 500 milliseconds
Input / Output isolationGalvanic
Temperature0°C to + 55°C
HumidityUp to 95% Rh non condensing
Dimensions (L x W x D) (mm)75 x 56.5 x 117.5
Weight440 gms
Output RippleLess than 0.5% of span (peak to peak)
Auxiliary Supply BurdenLess than 4 VA
Insulation ResistanceMore than 100 Mohms at 500 V DC
Zero Span AdjustmentOptionally provided
TerminalsSuitable for 2.5 sq.mm wires
Enclosure TypeABS Plastic, Ingress Protection IP40
IEC Standard60688
Auxiliary Supply
Auxiliary18 - 60 / 24/48 VDC +/- 20%, 80-300 VAC / DC, 50 Hz
Input Value
I in0 - 1 A AC / 0 - 5 A AC
Output Load Resistance (Rout)
For Current OutputMax. 10V/I out (Optional Max. 15V/Iout)
For Voltage Output10 Kohm (min.)
Product
ApplicationsSpeed Control Feedback Application, Metering & Relay Panels for Substations