Minilec D2 MPR3 Motor / Pump Protection Relay
- Brand
- Minilec
- Model number
- D2 MPR3
- Category
- Motor Protection Relays
Minilec D2 MPR3 motor / pump protection relay with 2 CO output. Typical uses: air -conditioning & refrigeration machines, crusher motors , mining m/c, screw compressors.
Price and availability on request
Key features
- Overload & Dry Run, Unbalance
- Auto/Manual Reset
- Testing Facility
- UC Bypass Facility
- Phase Failure, Phase Sequence
- Adjustable Trip Settings
- Selectable Overload Characteristics
- 2 CO Output Relay
Specifications
| Input | from S2 CTS 1 |
|---|---|
| Output Contacts | 2 CO |
| Weight | 250 gms (Approx.) |
| Note | Wherever not specified Contact Rating : 5A @ 230 V AC (resistive) |
| Auxiliary | 100 - 120 / 220 - 240 / 380 - 440 V AC ± 20%, 48 - 63 Hz |
|---|
| Phase to Phase Unbalance | 50% of Motor Current ± 10% (Fixed) |
|---|---|
| Under Current (Dry Run) | 40% to 80% ± 5% of Set Current (Adjustable with Bypass Facility) |
| Over Load | As per IDMTL Characteristics |
| On Phase Failure | 4.0 Sec ± 1.0 Sec |
|---|---|
| Over Load | As per IDMTL Characteristics 2 Sec. (Fixed) |
| Reset | Auto / Manual / Remote |
|---|
| Overall (L x W x D) | 76 x 56.5 x 117.5 |
|---|---|
| Mounting (L x W) | 67 X 46 / 35 mm Rail Mounting |
| Applications | Air -Conditioning & Refrigeration Machines, Crusher Motors , Mining M/c, Screw Compressors, End Users, Lift , Elevators, Hoist & Cranes |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.